Parameter
Parameter Name Parameter Range Default
Code
N16
Auxiliary heat
source on/off
N17
IDU's anti-cold wind
temperature setting
in heating mode
N18
Fan speed in cooling
standby mode
N19
Standby fan speed
L1 range in dry mode
N20
Fan speed in heating
standby mode
N21
Time to stop the fan
of IDU in heating
mode (Termal)
N22
EXV opening during
heating standby
N23
Cooling return
difference
temperature
N24
Heating return
difference
temperature
N25
IDU heating
temperature
compensation
N26
IDU cooling
temperature
compensation
Value
00/01/02
00
00/01/02/03/04
00
00/01/02/03/04/05/06
01
/07/14
00/01/02/03
01
00/01/14
00
00/01/02/03/04
01
00/01/02/14
14
00/01/02/03/04
00
00/01/02/03/04
00
00/01/02/03/04
00
00/01/02/03/04
00
47
Remarks
00: Auto; 01: Forced on; 02: Forced off
Common IDU:
0: 15; 1: 20; 2: 24; 3: 26; 04: Anti-cold wind disabled
Fan coil unit: 00: 32°C; 01: 34°C; 02: 36°C; 03: 38°C;
04: anti-cold wind invalid
00: Fan off after a delay
01: Speed 1; 02: Speed 2
03: Speed 3; 04: Speed 4
05: Speed 5; 06: Speed 6
07: Speed 7; 14: Fan speed before entering standby mode
00: Fan off; 01: L1; 02: L2; 03: Speed 1
0: Termal; 1: Speed 1
14: Fixed to Speed 1
00: Stop the fan; 01: 4min; 02: 8min; 03: 12min;
04: 16min (stop the fan for Xmin; open the fan at speed
1 for 1min to detect the actual T1 temperature)
00: 56P; 01: 72P; 02: 00P; 14: Auto adjustment
00: 1°C; 01: 2°C; 02: 0.5°C; 03: 1.5°C; 04: 2.5°C
00: 1°C; 01: 2°C; 02: 0.5°C; 03: 1.5°C; 04: 2.5°C
00: 6°C 01: 2°C 02: 4°C 03: 8°C 04: 0°C
00: 0°C; 01: 1°C; 02: 2°C
03: 3°C; 04: -1°C