Siemens SIMATIC NET ET 200SP Instructions De Service page 95

Masquer les pouces Voir aussi pour SIMATIC NET ET 200SP:
Table des Matières

Publicité

Types de points de données du protocole "CEI 60870-5"
Tableau 4- 5 Types de points de données, types CEI pris en charge et types de données S7 compatibles
Format (espace
Type de point de données
mémoire requis)
Bit
Single-point information
Single-point information with time tag
CP56Time2a
Single command
Single command with time tag
CP56Time2a
Octet
Step position information
Step position information with time
tag CP56Time2a
Entier (16 bits)
Measured value, normalized value
Measured value, normalized value
with time tag CP56Time2a
Measured value, scaled value
Measured value, scaled value with
time tag CP56Time2a
Set point command, normalised
value
Set point command, scaled value
Set point command, normalised
value with time tag CP56Time2a
Set point command, scaled value
with time tag CP56Time2a
Entier (32 bits)
Bitstring of 32 bits
Bitstring of 32 bits with time tag
CP56Time2a
Integrated totals
Integrated totals with time tag
CP56Time2a
Bitstring of 32 bits
Bitstring of 32 bits with time tag
CP56Time2a - control direction
Nombre à virgule
Measured value, short floating point
flottante (32 bits)
number
Measured value, short floating point
number with time tag CP56Time2a
Set point command, short floating
point number
Set point command, short floating
point with time tag CP56Time2a
Bloc de données
Double-point information
(1...2 Bit)
2)
Double-point information with time
tag CP56Time2a
CP 154xSP-1
Instructions de service, 02/2018, C79000-G8977-C426-04
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
4.7 Telecontrol (CP 1542SP-1 IRC)
Type CEI
Direction
Types de don-
nées S7
<1>
in
Bool
<30>
in
Bool
<45>
out
Bool
<58>
out
Bool
<5>
in
Byte, USInt
<32>
in
Byte, USInt
<9>
in
Int
<34>
in
Int
<11>
in
Int
<35>
in
Int
<48>
out
Int
<49>
out
Int
<61>
out
Int
<62>
out
Int
<7>
in
UDInt, DWord
<33>
in
UDInt, DWord
<15>
in
UDInt, DWord
<37>
in
UDInt, DWord
<51>
out
UDInt, DWord
<64>
out
UDInt, DWord
<13>
in
Real
<36>
in
Real
<50>
out
Real
<63>
out
Real
<3>
in
<31>
in
Configuration
Zone d'opérandes
I, Q, M, DB
I, Q, M, DB
Q, M, DB
Q, M, DB
I, Q, M, DB
I, Q, M, DB
I, Q, M, DB
I, Q, M, DB
I, Q, M, DB
I, Q, M, DB
Q, M, DB
Q, M, DB
Q, M, DB
Q, M, DB
I, Q, M, DB
I, Q, M, DB
I, Q, M, DB
I, Q, M, DB
Q, M, DB
Q, M, DB
Q, M, DB
Q, M, DB
Q, M, DB
Q, M, DB
DB
2)
DB
2)
95