Settings, Mass configuration / initial commissioning
Confirm the newly connected sensor on the CMC III PU 19" Edition website.
Alternatively, the newly connected sensor can also be confirmed locally via the display. To do this:
EN
In the Rittal main menu, select the "Setup" entry and confirm your entry by pressing the "Return" key.
Select the "Sensor" entry and press the "Return" key to confirm your selection. The menu for entering
your security PIN will appear.
Enter the required security PIN (see section 6.1 "Settings via the display") then confirm the entry "Ac-
knowledge All Devices" by clicking on "Return".
Status change display on the CAN bus LEDs:
– Continuous green LEDs: CAN bus status "OK".
– Continuous red LEDs: CAN bus status faulty.
Status change display on the multi-LED of the CMC III PU 19" Edition:
– Continuous green light: The CMC III PU 19" Edition and all devices connected to the CAN bus have
the status "OK".
– Continuous orange light: The CMC III PU 19" Edition or at least one device connected to the CAN
bus has the status "Warning".
– Continuous red light: The CMC III PU 19" Edition or at least one device connected to the CAN bus
has the status "Alarm".
Status change display on the multi-LED of the connected sensor.
– Continuous blue flashing: Communication via the CAN bus.
– Green flashing: When the measured value changes or, at the latest, every 5 seconds.
Further sensors are connected as daisy chain.
If necessary, connect another component (e.g. another sensor type) to the second, free CAN bus
interface of the first component.
Proceed in the same way for further components (up to 16 units in total).
Note:
Further information concerning the connection and configuration of sensors can be found
in the associated documentation of the accessory part.
7
Mass configuration / initial commissioning
To allow easy and quick commissioning of several CMC III PUs, they can be preconfigured using a spe-
cial configuration file. The configuration file copied to a USB data carrier allows several CMC III PUs to
be configured in just a few minutes without an operational network connection being required. To edit
the file on a PC, either the CMC III PU serial numbers, or at least one of the two MAC addresses of the
CMC III PU network interfaces, is required. A predefined sample file as well as a description of the pro-
cedure can be found on the CMC III PU 19" Edition product pages at our website.