can alter the parameter value by pressing the "Set" pushbutton and
confirm the new value by pressing the "Mode/Enter" pushbutton. The
internal sensing, processing and output functions of the unit continue
as if in Run mode with the original parameter values unless a new
value is confirmed. The unit returns to the Run mode when no push-
button has been pressed for 15 s.
Technical information / Operation / Parameters
Adjustable parameters
Switch-on point 1 / 2
Upper limit value at which the output changes its switching
status.
SPx is only active if OUx = Hno, Hnc, Fno or Fnc.
Switch-off point 1 / 2
Lower limit value at which the output changes its switching
status.
rPx is always lower than SPx. The unit only accepts values which
are lower than SPx.
Changing the switch-on point also changes the switch-off point
(the distance between SPx and rPx remains constant).
If the distance is higher than the new switch point, it is automa-
tically reduced (rPx is set to the minimum setting value).
rPx is only active if OUx = Hno, Hnc, Fno or Fnc.
Setting ranges: (standard volume flow):
Nm
Nl/min
Pulse / Counter settings
Determines the pulse value / value for the preset counter.
Setting range: 0.005 ... 4 000 000 Nm
Pulse length: min. 0.037 s / max. 2 s.
ImPS is only active if OU1 = ImP.
Setting of the value (→ page 31).
SP1 / SP2
3
3.5 ... 417.0
/h
60 ... 6950
rP1 / rP2
1.5 ... 415.0
30 ... 6920
3
.
in steps of
0.5
10
35