Technical Information / Operation / Parameters; Adjustable Parameters - Schmidt SS 30.300 Notice D'utilisation

Publicité

Les langues disponibles

Les langues disponibles

can alter the parameter value by pressing the "Set" pushbutton and
confirm the new value by pressing the "Mode/Enter" pushbutton. The
internal sensing, processing and output functions of the unit continue
as if in Run mode with the original parameter values unless a new
value is confirmed. The unit returns to the Run mode when no push-
button has been pressed for 15 s.

Technical information / Operation / Parameters

Adjustable parameters

Switch-on point 1 / 2
Upper limit value at which the output changes its switching
status.
SPx is only active if OUx = Hno, Hnc, Fno or Fnc.
Switch-off point 1 / 2
Lower limit value at which the output changes its switching
status.
rPx is always lower than SPx. The unit only accepts values which
are lower than SPx.
Changing the switch-on point also changes the switch-off point
(the distance between SPx and rPx remains constant).
If the distance is higher than the new switch point, it is automa-
tically reduced (rPx is set to the minimum setting value).
rPx is only active if OUx = Hno, Hnc, Fno or Fnc.
Setting ranges: (standard volume flow):
Nm
Nl/min
Pulse / Counter settings
Determines the pulse value / value for the preset counter.
Setting range: 0.005 ... 4 000 000 Nm
Pulse length: min. 0.037 s / max. 2 s.
ImPS is only active if OU1 = ImP.
Setting of the value (→ page 31).
SP1 / SP2
3
3.5 ... 417.0
/h
60 ... 6950
rP1 / rP2
1.5 ... 415.0
30 ... 6920
3
.
in steps of
0.5
10
35