Télécharger Imprimer la page

Schmidt SS 30.300 Notice D'utilisation page 228

Publicité

Les langues disponibles

Les langues disponibles

Pulse repetition
Determines which signals are provided by the meter at output 1,
2 settings can be selected:
• YES: Pulse repetition active (= simple counter function):
Output 1 provides a counting pulse every time the value set in
ImPS is reached.
• no: Pulse repetition not active (the counter operates as a pre-
set counter): Output 1 switches (OUT1 = ON) when the value
set in ImPS is reached. It remains switched until the counter is
reset (→ page 37, parameter rTo).
ImPR is only active if OU1 = ImP.
Configuration of output 1
5 settings can be selected:
- Output signals for flow rate:
• Hno = hysteresis function / normally open
• Hnc = hysteresis function / normally closed
• Fno = window function / normally open
• Fnc = window function / normally closed
- Output signal for the meter:
• ImP = Pulse sequence or On / Off signal for preset counter
(→ parameter ImPS and ImPR)
Configuration of output 2
4 switching functions and 1 analogue signal can be set for flow
rate:
• Hno = hysteresis function / normally open
• Hnc = hysteresis function / normally closed
• Fno = window function / normally open
• Fnc = window function / normally closed
• I = analogue signal (4 ... 20 mA)
Analogue start point
Measured value at which 4 mA is provided.
ASP is only active if OU2 = I .
Analogue end point
Measured value at which 20 mA is provided.
Minimum distance between ASP and AEP = 25% of the final
value of the measuring range. AEP is only active if OU2 = I .
Setting ranges: (standard volume flow):
Nm
Nm
36
ASP
3
0 ... 532
/h
3
0,00 ... 8,86
/min
AEP
180 ... 712
3,00 ... 11,87
in steps of
1
0,01

Publicité

loading