Pulse repetition
Determines which signals are provided by the meter at output 1,
2 settings can be selected:
• YES: Pulse repetition active (= simple counter function):
Output 1 provides a counting pulse every time the value set in
ImPS is reached.
• no: Pulse repetition not active (the counter operates as a pre-
set counter): Output 1 switches (OUT1 = ON) when the value
set in ImPS is reached. It remains switched until the counter is
reset (→ page 37, parameter rTo).
ImPR is only active if OU1 = ImP.
Configuration of output 1
5 settings can be selected:
- Output signals for flow rate:
• Hno = hysteresis function / normally open
• Hnc = hysteresis function / normally closed
• Fno = window function / normally open
• Fnc = window function / normally closed
- Output signal for the meter:
• ImP = Pulse sequence or On / Off signal for preset counter
(→ parameter ImPS and ImPR)
Configuration of output 2
4 switching functions and 1 analogue signal can be set for flow
rate:
• Hno = hysteresis function / normally open
• Hnc = hysteresis function / normally closed
• Fno = window function / normally open
• Fnc = window function / normally closed
• I = analogue signal (4 ... 20 mA)
Analogue start point
Measured value at which 4 mA is provided.
ASP is only active if OU2 = I .
Analogue end point
Measured value at which 20 mA is provided.
Minimum distance between ASP and AEP = 25% of the final
value of the measuring range. AEP is only active if OU2 = I .
Setting ranges: (standard volume flow):
Nm
Nm
36
ASP
3
0 ... 532
/h
3
0,00 ... 8,86
/min
AEP
180 ... 712
3,00 ... 11,87
in steps of
1
0,01