Make Electrical Connection

WARNING
Electrical Shock Hazard
Disconnect power before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
1. Disconnect power.
2. Remove terminal box cover.
3. Remove the knockout in the terminal box cover and install a
UL listed or CSA approved ¹⁄₂" strain relief.
4. Run 3 wires, black, white and green (14AWG), in ¹⁄₂" conduit
from service panel to terminal box. Use caulking to seal
opening.
A
C
D
A. UL listed or CSA approved strain relief
B. Home power supply cable
C. Terminal box
D. Black wires
E. Green (or bare) wire connected to yellow-green wire
F. White wires
5. Use UL listed wire connectors and connect black wires (D)
together.
6. Use UL listed wire connectors and connect white wires (F)
together.
10
B
E
F
WARNING
Electrical Shock Hazard
Electrically ground blower.
Connect ground wire to green and yellow ground wire
in terminal box.
Failure to do so can result in death or electrical shock.
7. Connect green (or bare) ground wire from home power supply
to yellow-green ground wire (E) in terminal box using UL listed
wire connectors.
8. Tighten strain relief screw.
9. Install terminal box cover.
10. Check that all light bulbs are secure in their sockets.
11. Reconnect power.

Install Vent Covers

Push lower cover down onto hood and lift upper cover to ceiling
and install with two 2.9 x 6.5 mm screws.
NOTE: For vented installations the upper vent cover may be
reversed to hide slots.
A
A. Vent cover bracket
B. Upper vent cover
C. Lower vent cover
D. 2.9 x 6.5 mm screws
D
D
B
C