Protective earth conductor for housing cover at module housing bottom
Size
M6
▶ Mount cable lug with toothed washer.
Protective earth conductor at shield connection plate
Size
M6
▶ Mount the screwed connection in this order: toothed washer, cable lug, washer, thrust washer, nut.
Protective earth conductor of power connection to CSV.
This power connection is screwed into the head of a threaded rod.
• 40 Nm (M10): Tightening torque of protective earth conductor in der threaded rod
• 42 Nm (M12): Tightening torque of the threaded rod itself
FI current bars at CSV.
Size
M10
M12
▶ Mount the screwed connection M10 in this order: screw, pair of wedge lock washers, current bar, FI connection,
pair of wedge lock washers, nut.
11 Document as PDF
Open document as PDF
CT-311-5 // PDF Download
Nut
4 Nm
Nut
5 Nm
56 Nm
60 Nm
47