EN: Installation Sheet
Description
The 2010-2A-ZI Zone LED Indicator Boards provide up to 40
zone status LED indicators.
Caution:
The 2010-2A-ZI Zone LED Indicator Boards are only
compatible for installation in Aritech 2X-A and Ziton ZP2-A
addressable control panels.
Table 1: 2010-2A-ZI Zone LED Indicator Boards
Model
Zones
2010-2A-ZI-20
20
2010-2A-ZI-40
40
2010-2A-ZI-24-S
24
Two LEDs are used to indicate zone events and status for
each zone.
The red LED indicates an alarm in the corresponding zone:
A flashing red LED indicates a detector (or automatic) fire
alarm
A steady red LED indicates a manual call point fire alarm
The yellow LED indicates a fault, test, or disablement in the
corresponding zone:
A flashing yellow LED indicates a fault
A steady yellow LED indicates that the zone is disabled or
is being tested
Installation
WARNING:
To avoid personal injury or death from
electrocution, disconnect the control panel from the mains
power supply and batteries before installing this product.
To install the zone indicator board:
1.
Unscrew and remove the plastic cover from the inside of
the control panel door. See Figure 1 for screw locations.
2.
Install the zone indicator board inside the control panel
door as shown in Figure 2.
Push the board upwards to connect the zone indicator
board to the J13A connector on the PCB above. Align the
screw holes and secure the board using the screws and
washers provided.
3.
Number the zones on the inserts provided (see Figure 3)
and then add the inserts to the board as shown in
Figure 4.
4.
Restore power and add the zone indicator board to the
control panel configuration (see your control panel
installation manual for more information).
2 / 23
www.acornfiresecurity.com
Compatible panel
Large panel
Large panel
Small panel
www.acornfiresecurity.com
Specifications
Maximum number of zones
2010-2A-ZI-20
2010-2A-ZI-40
2010-2A-ZI-24-S
Typical current consumption (active) [1]
2010-2A-ZI-20
2010-2A-ZI-40
2010-2A-ZI-24-S
Typical current consumption (standby) [2]
Weight
2010-2A-ZI-20
2010-2A-ZI-40
2010-2A-ZI-24-S
Dimensions (W × H)
2010-2A-ZI-20
2010-2A-ZI-40
2010-2A-ZI-24-S
Environmental
Operating temperature
Storage temperature
Relative humidity
[1] All LEDs on
[2] All LEDs off
Regulatory information
Conformity
Carrier Manufacturing Poland Spółka Z o.o.,
Manufacturer
Ul. Kolejowa 24, 39-100 Ropczyce, Poland.
Authorized EU manufacturing representative:
Carrier Fire & Security B.V., Kelvinstraat 7, 6003 DH
Weert, Netherlands.
Contact information and product
documentation
For contact information or to download the latest product
documentation, visit firesecurityproducts.com.
Product warnings and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE TO AND
INSTALLATION BY QUALIFIED PROFESSIONALS.
CARRIER FIRE & SECURITY B.V. CANNOT PROVIDE ANY
ASSURANCE THAT ANY PERSON OR ENTITY BUYING ITS
PRODUCTS, INCLUDING ANY "AUTHORIZED DEALER" OR
"AUTHORIZED RESELLER", IS PROPERLY TRAINED OR
EXPERIENCED TO CORRECTLY INSTALL FIRE AND
SECURITY RELATED PRODUCTS.
For more information on warranty disclaimers
and product safety information, please check
https://firesecurityproducts.com/policy/product-
warning/ or scan the QR code:
P/N 00-3301-501-6000-02 • ISS 14DEC22
20
40
24
12 mA at 24 VDC
14 mA at 24 VDC
12 mA at 24 VDC
2.2 mA at 24 VDC
135 g
140 g
50 g
267 x 152 mm
267 x 152 mm
267 x 63 mm
–5 to +40°C
–20 to +50°C
10 to 95% noncondensing