Télécharger Imprimer la page

Circutor M361B01-02-24B Manuel D'instructions page 116

Analyseur de réseaux

Publicité

8�4�1�- CARTE PICS
PICS
Vendor Name:
Product Name:
Product Model Number:
Application Software Version: 1.1
Firmware Revision:
BACnet Protocol Revision:
Product Description:
Electrical energy meter
BACnet Standardized Device Profile (Annex L)
x
List all BACnet Interoperability Building supported (see Annex K in BACnet Addendum 135d):
DS-RP-B Read Property
DS-WP-B Write Propery
DS-RPM-B Read Property Multiple
DM-DDB-B Dynamic Device Binding
DM-DOB-B Dynamic Object Binding
DM-DCC-B Device Communication Control
DM-RD-B Reinitialize Device
Which of the following device binding methods does the product support? (check one or more)
x
x
Standard Object Types Supported:
Analog Input Object Type
1. Dynamically creatable using BACnet's CreateObject service?
2. Dynamically deleatable using BACnet's DeleteObject service?
3. List of optional properties supported:
4. List of all properties that are writable where not otherw is a required by this standard
5. List of proprietary properties:
6. List of any property value range restrictions:
Properly Identifier
Object_Name
DESCRIPTION
Tensión fase-neutro
Corriente
Potencia activa
Potencia reactiva
Factor de potencia
Tensión fase-neutro
Corriente
Potencia activa
116
CIRCUTOR
CVM-C11
0870
0.8.4
12
BACnet Application Specific Controller (B-ASC)
Recive Who-Is, send I-Am (BIBB DM-DDB-B)
Recive Who-Has, send I-Have (BIBB DM-DOB-B)
max 32 characters
Voltage phase to neutral
Current
Active power
Reactive power
Power factor
Voltage phase to neutral
Current
Active power
No
No
max_pres_value
SYMBOL
ID OBJECTS
V 1
AI0
A 1
AI1
kW 1
AI2
kvar 1
AI3
PF 1
AI4
V 2
AI5
A 2
AI6
kW 2
AI7
CVM-C11
min_pres_value
OBJECT NAME
UNITS
Ph2NU1
V
Ph1Current
A
ActPwrPh1
kW
ReactPwrPh1
kvar
PwrFactPh1
PF
Ph2NU2
V
Ph2Current
A
ActPwrPh2
kW
Manuel d'instructions