PE Connection / Schutzerdungs-Anschluss / Connexion PE / Conexión PE / Ligação à
Terra / PE-aansluiting / Collegamento PE / Połączenie PE / PE připojení / PE-anslutning
/ Conexiune PE / PE връзка (земя) / Jordforbindelse / Σύνδεση PE / PE ühendus /
PE-yhteys / PE priključak / PE bekötés / PE (apsauginio įžeminimo) kontaktas / PE
savienojums / Pripojenie ochranného vodiča / PE povezava / PE Bağlantısı / Conexão
PE / ‫ ليصوت‬PE (‫)يئاقولا يضرألا‬
6.4 mm
1
Length=8-10 mm
3
For the grounding cable between BMS and battery, see figure below.
*Note: For the end of the grounding cable connecting to the inverter, please refer to the User Manual of
5
the inverter.
In case of a rated current of 30 A, the wire size of 5.5-6.5 mm² for cables (including
grounding cable) is recommended; in case of a rated current of 45 A, the wire size of 8.5-9.5
mm² for cables (grounding cable) is recommend.
*Note: The grounding cable should be prepared by the users themselves.
6-10 mm²
Length=28-30 mm
Heat-shrink tubing
2
4
M5
1 N·m
to inverter