A 1.. A10
Once the cabinet temperature, related to a present temperature alarm (A 0), is no longer
outside the alarm ranges, this A 0 alarm becomes the new A 1. Etc.
Use
and
to navigate between the different alarms.
Push
to open a temperature alarm in order to show:
Example 1 – alarm A 0: (Present temperature alarm)
Ah
Indicating it is a high temperature alarm (AL indicating a low temperature alarm)
10.0 the maximum temperature in °C during the alarm (If AL the minimum temperature)
dur
alarm duration until now
01h
the alarm has been ongoing for 1 hour
.... and 15 minutes
15'
Example 2 – alarm A1 to A10: (alarms in the log – not present)
Ah
Indicating it is a high temperature alarm (AL indicating a low temperature alarm)
11.0 the maximum temperature in °C during the alarm (If AL the minimum temperature)
dur
alarm duration
01h
the alarm lasted for 1 hour
.... and 15 minutes
15'
tSE
time since the end of the alarm
08h
the alarm ended 8 hours ago
Each value is displayed alternately for approx. 1 second.
It is not possible to reset or delete a present temperature alarm A 0
Resetting alarm symbol
Look through all non-present alarms, after each alarm Push
alarm. To exit an alarm without verifying, push
turn off, unless there is a present alarm.
Push
, to leave alarm log.
Deleting alarms:
Push
once to open the log.
Display shows A 1. Delete all non-present temperature alarms by holding
Once the alarm log is deleted the display flashes " - - - " for 3 seconds.
Messages and alarms shown in the display
OP
OP shown constantly, indicates door open. If alternating with temperature, door
has been open for more than 2 minutes. Close the door and OP will disappear.
E1
E1 indicates defective room sensor. Monitor temperature until replaced.
Request service assistance immediately.
E2
Alternating between E2 and temperature indicates defective evaporator sensor.
Defrosting will be time-based. (freezer) Request service assistance.
Alarm high temperature – See explanation under temperature alarms
Ah
765042402
Not present temperature alarms logged
(maximum 99 hours)
. Once all alarms have been verified,
Rev. 005
to verify having seen the
for 5 seconds.
will
39