dAh should never be adjusted to less than 30 minutes.
To access the temperature alarm parameters, push and hold
5 seconds. The display will flash the first temperature alarm parameter hAL.
To access the individual parameters push
To move between and adjust the parameters use
Push
to store the new setting. The controller automatically jumps to the next parameter.
Adjustable parameters are:
hAL
High Alarm Limit
LAL
Low Alarm Limit
dAh
Time delay Alarm high
dAL
Time delay Alarm Low
Atd
Alarm temperature differential
The above parameter settings will result in the following:
To trigger a high temperature alarm (Ah) the cabinet temperature must be above hAL = 25°C
for more than dAh = 120 minutes. This will result in
between Ah and the present cabinet temperature.
Once the temperature goes below 23°C (hAL – Atd) the alarm changes from present to
being logged. The display will show current temperature and
has been a temperature alarm.
To trigger a Low temperature alarm (AL) the cabinet temperature must be below LAL = -
29°C for more than dAL = 20 minutes. This will result in
between AL and the present cabinet temperature.
Once the temperature goes above -27°C (LAL + Atd) the alarm changes from present to
being logged. The display will show current temperature and
has been a temperature alarm.
Temperature alarms
The following temperature alarms can be displayed:
Ah
Alarm high temperature
AL
Alarm Low temperature
If an alarm occur, Ah or AL will be shown alternating with the current temperature.
If the temperature gets back within the accepted limits, the current temperature will be shown
in the display and
off, but the alarm will still be kept in the alarm log.
Displaying alarms:
The temperature alarm log stores information related to the latest 10 temperature alarms
(named A 1 to A10). If a new alarm occurs the oldest alarm (A10) will be erased.
Push
once to open the log.
• If there is no present or logged temperature alarm the display will show "no" flashing
for 4 seconds. After that the controller will revert to normal operation.
• If there are present or logged temperature alarms the display will show the most recent
temperature alarm being:
A 0
765042402
will remain lit until the alarm has been reset. After 3 days
Present / ongoing temperature alarm.
.
and
Factory default
+ 25° C
- 29° C
120 minutes
20 minutes
2K
being lit and the display alternating
being lit and the display alternating
Rev. 005
and
simultaneously for
.
will remain lit indicating there
will remain lit indicating there
will be turned
38