Code Zone 1
3-pol. + PE
3-pol. + N + PE
Dimensions in mm
X = fixing dimensions
Wall socket,
4- and 5-pole
Explosion-protected plugs and sockets
63A, GHG 514
1
Technical data
1.1
Plug and socket GHG 514
Marking acc. to 2014/34/EU and standard:
EN 60079-0
ATEX type examination certificate:
Rated voltage:
Rated current:
Back-up fuse:
without thermal protection
with thermal protection
Switching capacity AC 3:
Perm. ambient temperature:
Special versions permit deviating temperatures.
Perm. storage temperature in original packing:
**Protection category acc. to IEC/EN 60529
with closed and secured hinged cover as well
as combinations properly plugged together
Insulation class acc. to IEC/EN 61140:
Cable entry:
wall socket
suitable cables and test torques of the
pressure srew
Seal 1+2+3
min.
1 2
3
max. (1)(2)
Seal 1+2
min.
1 2
3
max. (1)(2)
Seal 1
min.
1 2
3
max. (2)
Test torque for screw in thread cable entry (Nm)
(1) The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use the
combination of sealing 1 + 2 + 3 for the intermediate region.
(2) When selecting the seal rubber, ensure that the cap nut can be tightened when carrying out any future
maintenance work on the cable entry.
plug
Supply terminal:
wall socket
plug
Test torques:
Cover screws
Terminals, plug
Terminals, wall socket
Self-cutting screws size 4
Self-cutting screws size 5
Self-cutting screws size 8
Weight:
wall socket
4-pole
GHG 514 44
plug
4-pole
GHG 514 74
wall socket
5-pole
GHG 514 45
plug
5-pole
GHG 514 75
Auxiliary contact:
Rated voltage:
Rated current:
Switching capacity:
D II 2 G Ex de II C T6
D II 2 D Ex tD A21 IP66 T 80°C**
PTB 00 ATEX 1070
up to 690 V, 50/60 Hz
max. 63 A
max. 63 A
max. 80 A gL
up to 690 V / 63 A
-20° C to +40° C (catalogue version)
-20° C to +40° C
IP 66 (catalogue version)
I - is complied with by the devices
(catalogue version)
1x M50 + 1x blanking plug M50
Ø
Nm
--
--
24.0
6.0
28.0
7.0
28.0
5.0
35.0
7.0
7.5
Ø 19 - 34 mm
Cross section
Stripped wire length
2 x 4 - 25 mm²
19 mm
(with cable lugs 1 x 35 mm²)
1 x 4 - 16 mm²
12 mm
(with cable lugs 1 x 25 mm²)
2.50 Nm
2.40 Nm
3.50 Nm
2.00 Nm (Page 10, Pos.10)
3.00 Nm (Page 10, Pos.5)
3.50 Nm
(catalogue version)
approx. 8.10 kg
approx. 0.75 kg
approx. 8.15 kg
approx. 0.80 kg
690 V VAC
20 A
AC 15
400 V / 6 A
DC 13
24 V / 2 A
Plug,
4- and 5-pole
GB
7