Fig. 1
Wall mounting bracket
side
Fig. 2
7
9
2
Safety instructions
This „Annex to operating
instructions"
GHG 5107003P0011 is only for
use with the original operating
instructions
"GHG 510 7003 P0001" . The GHG 514 plugs
and sockets are not suitable for Zone 0 and
Zone 20 hazardous areas.
Observe the national safety rules and
regulations for prevention of accidents as
well as the safety instructions included in
these operating instructions and set in
italics the same as this text!
Explosion-protected plugs and sockets 63 A, GHG 514
1
Technical data
1.1 Plug and socket GHG 514
top/bottom
Marking acc. to 94/9/EG and standard:
EN 60079-0
IECEX type examination certificate:
Category of application:
IEC60079-0
Rated voltage:
Rated current:
Back-up fuse:
without thermal protection
with thermal protection
Switching capacity AC 3:
Perm. ambient temperature:
catalogue version, special versions permit deviating
temperatures.
Perm. storage temperature in original packing: -20° C to +40° C
**Protection category acc. to IEC/EN 60529
with closed and secured hinged cover as well
as combinations properly plugged together
Insulation class acc. to IEC/EN 61140:
Cable entry:
wall socket
Supply terminals:
terminals L, N
terminals PE
Test torques:
Cover screws
Terminals
Weight:
wall socket
Auxiliary contact:
Rated voltage:
Rated current:
Switching capacity:
3
Field of application
The plugs and sockets GHG 514 are suitable
for use in Zone 1, 2 and 21, 22 hazardous
areas acc. to IEC/EN 60079-10-1 and
IEC/EN 60079-10-2!
The enclosure materials employed, including
the exterior metal parts, are made of high-
quality materials which ensure a corrosion
protection and resistance to chemical sub-
stances corresponding to the requirements in
a "normal industrial atmosphere":
- impact resistant polyamide
- glass-fibre reinforced polyester
- special steel AISI 316 L
In case of use in an extremely aggressive
atmosphere, please refer to manufacturer.
single-wire connection
multi-/ fine-wire connection
single-/ multi-wire connection
4/5-pole
GHG 514 45
PTB 00 ATEX 1070
II 2 G Ex de IIC T6
II 2 D Ex tD A21 IP66 T80°C
IECEX BVS 12.0027
Ex de IIC T5/T6 Gb
Ex tb IIIC T80°C Db IP66
up to 690 V, 50/60 Hz
max. 63 A
max. 63 A
max. 80 A gL
up to 690V / 63A
-20° C to +40° C
IP 66 (catalogue version)
II - is complied with by the devices
(catalogue version)
2x blanking plug M50
Cross section
Stripped wire length
16 mm²
30 mm
16 mm² - 95 mm²
30 mm
35 mm² - 135 mm²
35 mm
2,5 Nm
12 Nm
(catalogue version)
approx. 18.6 kg
690V VAC
20A
AC 15
400V / 6A
DC 13
24V / 2A
4
Use/Properties
The GHG 514 plugs and sockets are used for
the power supply of local controls with varying
locations, as well as of electrical installations,
mobile machinery and driving gear in hazard-
ous areas. The plugs and sockets can also be
used in a „normal industrial area" .
The low-voltage plugs and sockets GHG 514
are fitted with a load break switch and can be
used up to max. 63 A (see technical data).
The plugs and sockets can generally be used
for the voltage range laid down in EN 60309
(e.g. U
400V that corresponds to the voltage
N
range 380-415V).
The apparatus connected to the plug shall
be suitable for the applied mains voltage.
The plug can be pushed into the socket and
pulled out of it only whilst the socket ist
switched off.
In order to switch on the socket, the plug is
inserted, pushed fully home.
GB
5