8. CONFIGURATION OF OTHER
OPERATING MODES.
8.1. BYPASS.
Fig. 38. Control keys.
"ESC"→ Exits the main menu.
" → Previous control screen.
"
" → Next control screen.
"
"ENTER" → Executes a control command.
When the "Go to bypass" command is executed, confirma-
tion is requested and the display immediately shows the
i
message "
Done". Similarly, when the "Switch to normal mode"
command is executed, the display immediately shows the message
i
"
Done".
Messages will be displayed for 5 seconds and will then change
to the new available control option. So, if the UPS was in Normal
mode and the user selected "Switch to Bypass", the new option
available would be "Switch to Normal mode", and if the UPS was
in Bypass mode and the user selected "Switch to Normal mode",
the new option available would be "Switch to Bypass".
If the UPS is not in Normal or Bypass mode, this option is not active
and is not displayed as a control option.
Since it is only a manual request from the LCD display, the LCD
display settings and Bypass limits must be overridden and send
the UPS to "Static bypass". The alarm history log should indicate
"Static bypass".
If the UPS works in "Static bypass" and the bypass frequency is out
of range, the UPS will switch to Standby mode.
USER MANUAL
8.2. LOAD SEGMENTS.
Fig. 39. Load segments.
Default settings.
The default setting is "Segment 1 On". The system asks us to
confirm it or change it to Off.
Auto start delay: 3 s., load segment start time when the main
output of the UPS is turned on.
Auto shutdown delay: Disabled (99999).
Other options.
Automatic start-up delay: no delay (0), 1-99999.
Auto shutdown delay: 0-99998, load segment turn off time in
Battery mode.
8.3. BATTERY TEST.
Manual test.
Press "
" on the display to enter the main menu.
Press "
" on the display to select and enter the "Control"
menu.
Enter the "Control" menu to select and enter "Start battery test".
Fig. 40. Start battery test.
Automatic test.
The automatic battery test (enabled by default) is executed every
60 seconds with the batteries floating.
SLC TWIN RT3 0.7÷3 kVA UNINTERRUPTIBLE POWER SUPPLY (UPS)
67