4.1
Assembly of the actuator [specialist]
4.1.1 Actuator SR2 - DN 20 / SR5 – DN 25 + DN 32 / SR10 - DN 40 + DN 50
blue
When the actuator is
activated, it turns 90°
in clockwise direction!
16
1. Set the actuator to
manual mode by
turning the selector
switch. Only in the
manual mode, the lever
of the actuator can be
manually adjusted.
2. Turn the adjusting lever
to the left into the
position „blue".
3. Turn the rotary knob of
the 3-way valve such
that the nose points
downwards or to the
left to
.
4. Turn the actuator as
shown on the figure
and mount it to the
3-way valve.
5. Connect the actuator
to the controller.
6. Set the automatic
mode on the actuator.
The actuator is ready
for operation.
999608x-mub-ml – V09
4 Assembly and installation [specialist]
blue
When the actuator is activated,
it turns 90° in clockwise direction!
2017/01