Studer C-S Serie Manuel D'utilisation Et De Montage page 26

Publicité

Les langues disponibles

Les langues disponibles

STUDER Innotec
With the Push Button 19 (Change status) set the desired parameter (voltage or time)
to modify (LED 14/ 15/16/17/18). Push Button 19 (Change status) to set the desired
value according to the table 5.3.2.
If desired, repeat the operation with any other parameter (voltage or time) to be
changed.
If during 30 seconds no buttons are pressed, the selected values are automatically
stored and the COMPACT switches back in to the normal operating status.
The voltage levels and times changed through programming are only first active with
the next charge cycle!
The voltage level which is not suitable can greatly reduce the battery life or
could even destroy it ! Therefore check beforehand with your battery supplier.
5.3.2 Table of voltage and timing threshold
The voltage levels (low voltage, float charge, end of charge and equalization) and the
duration of the absorption charge can be changed.
The display of these voltages and the times in the program mode are in accordance
with the diagram shown below:
Low voltage
LED 13
12
24
48
14 12.0
24.0
48.0
13.7
15 11.8
23.6
47.2
13.6
16 11.6
23.2
46.4
13.5
17 11.4
22.8
45.6
13.4
18 11.2
22.4
44.8
13.3
The heavy printed values show the standard settings.
5.4
Auxiliary contact
5.4.1 Principle
The Auxiliary Contact can be basically programmed for any operating situation of the
COMPACT which is indicated with a LED. The programming is possible for one or
more operating situations. If the contact is programmed for many situations, it is
activated as soon as the COMPACT finds itself in any one of the programmed
situations. That means that the work of the contact meets that of the logic OR–
Function.
5.4.2 The programming of the Auxiliary Contact
The programming of the Auxiliary Contact is carried out in the following Steps:
− The Push Button 21 (Program) presses down for min. 2 seconds. The LED 4
„Program" is lit as an indication, that the COMPACT is in program mode.
− A blinking LED shows the programmed condition for the auxiliary contact (LED
10/11/ 12/13 factory setting).
− With the Push Button 20 (select), select the desired condition in which the
contact should be activated.
− With the Push Button 19 (Change status) confirm or change the status for this
condition. If desired, with the Push Button 20 (select) select another condition in
which the contact should be activated.
− With the Push Button 19 (Change status) confirm or change the status for this
condition. If during 30 seconds no buttons are pushed, then the settled values
Float charge
Absorption
LED 12
LED 11
12
24
48
12
27.4
54.8
16.2
32.4
27.2
54.4
15.6
31.2
27.0
54.0
15
26.8
53.6
14.4
28.8
26.6
53.2
14.2
28.4
COMPACT V6.4
Equalization
LED 10
24
48
12
24
64.8
16.2
32.4
64.8
62.4
15.9
31.8
63.6
15.6
31.2
62.4
30
60
57.6
15.3
30.6
61.2
56.8
15
30
COMPACT
Absorption
Equalization
time
time
LED
LED 10/11
10/11/12/13
48
12/24/48
12/24/48
4h
3h
2h
1h
60
0 – 1'
26/85
3h
2h
1h
40'
20'