STUDER Innotec
4.9
The Multifunctional Contact
In the COMPACT there is a built-in programmable power relay. The potential-free
change-over contact (NO – NC) of this power relay is connected to the screw
terminal AUX CONTACT.
Maximum Contact load: 230Vac / 12Vdc / 24Vdc / 16A !
With the Push Button 21 „AUXILIARY CONTACT" the contact can be manually
switched on or off independently from programming and from the operating situation.
The LED 5 "Contact active" shows the status of the contact. The drawing up the
screw terminal "AUX CONTACT" is the inactive position mode, LED 5 "Contact
active" off.
The switching on and off of this contact can be freely programmed for every
operating situation of the COMPACT witch situation is indicated with a LED. There is
no limitation to its application and it is left to your wishes as to where and how you
would like to use it. The example and the setting of this contact are explained in
chapter 5.4.
In factory we program this for a dysfunction alarm. The contact is active when one of
these situations is detected:
− Over temperature (LED 10 lit)
− Overload (LED 11 lit)
− Over or less voltage of batteries (LED 12 lit or blinking)
− COMPACT is turned off manually or with a fault (LED 13 lit)
In case this function is not wished, it must be modified by programming according to
procedure in chap. 5.4.
4.10 The Remote Control RCC-01
As an option, a Remote
Control can be connected to
the COMPACT. All operating
controls and displays except
from level adjustment are
available
on
the
Control. The Remote Control
is supplied with a 20m long
cable. It can as long as 40m.
The Remote Control is sui-
table for surface mounting on
the wall or on to a switch
board. It is fixed with 4
screws. The COMPACT can
also be programmed with the
Remote
Control.
Programming is descry-bed in
the section „Programming".
The output power and the charging currents are displayed on the Remote Control.
In the Remote Control there is an additional Alarm Contact and a built-in Control
Input. These two functions are available through Tip-jack RJ11/4 for use. This
Auxiliary Contact is Front / Work Contact (max. 0.5A!), which is independent from the
> 36Vdc / 3A !