LERBAKKEN 10, 8410 RØNDE DENMARK
For safe installation of 9202 the following must be observed. The module shall only be installed by
qualified personnel who are familiar with the national and international laws, directives and standards
that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
For Installation in Zone 2 / Division 2 the following must be observed.
The 4501 programming module is to be used solely with PR electronics modules. It is important that
the module is undamaged and has not been altered or modified in any way. Only 4501 modules free
of dust and moisture shall be installed.
IECEx Certificate
Marking 9202Bxx
Marking 9202Bxx, 9202Axx
Standards
Supply terminal (31,32)
Voltage:
Status Relay. terminal (33,34)
Voltage max:
Power max:
Current max:
Installation notes.
Install in pollution degree 2, overvoltage category II as defined in IEC60664-1.
Do not separate connectors when energized and an explosive gas mixture is present.
Do not mount or remove modules from the Power Rail when an explosive gas mixture is present.
Disconnect power before servicing.
The wiring of unused terminals is not allowed.
In type of protection [Ex ia Da] the parameters for intrinsic safety for gas group IIB are applicable.
For installation in Zone 2, the module shall be installed in an enclosure in type of protection Ex e,
providing a degree of protection of at least IP54. Cable entry devices and blanking elements shall
fulfill the same requirements.
For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit
type 9410 (Type Examination Certificate KEMA 07ATEX0152 X) is allowed.
Max. screw terminal torque 0.5 Nm.
Stranded wire should be installed with an insulation stripping length of 5 mm or via a suitable
insulated terminal such as a bootlace ferrule.
Revision date:
2022-02-14
IECEx Installation drawing
KEM 06.0039 X
[Ex ia Ga] IIC/IIB/IIA
[Ex ia Da] IIIC
[Ex ia Ma] I
Ex ec nC IIC T4 Gc
IEC60079-0: 2017, IEC60079-11:2011,
IEC60079-15 :2017, IEC60079-7:2015+A1:2017
19.2 – 31.2 VDC
125 VAC / 110 VDC
62.5 VA / 32 W
0.5 A AC / 0.3ADC
Version Revision
V6 R0
9202 - Version de produit 9202-003
9202QI01
Zone 2 Installation
32VAC / 32VDC
16VA / 32W
0.5A AC / 1ADC
Prepared by:
MMA
Page:
1/3