Télécharger Imprimer la page

Eaton EX RT 7/11 Manuel D'installation Et D'utilisation page 39

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 42
Permissible UPS overloads as a function of time
P/Pn
1.5
1.25
1.1
1.02
0.5s
30s
Short-circuit current provided by the UPS in Normal or Batterie mode
EX RT
7: 110 A for 80 ms.
z
EX RT 11
: 150 A for 80 ms.
z
Transformer EX RT
Nominal power
Nominal current
Input voltage
Voltage drop
Frequency
Isolation (EN 61558-1-2-4)
Operating temperature
Max. operating rel. humidity
Derating / altitude
Dimensions HxWxD (tower)
Dimensions HxWxD (rack 3U)
Weight
EX RT CLA module
AC input voltage: 160-280 Volts AC,
z
Input frequency: 40-70 Hz,
z
z
Battery charge current: 6 A DC,
Recharge time to recover 90 % of the rated backup time after discharge at full load:
z
EX RT 7
EX RT 11
Thermal characteristics
The operating temperature is 0 to 40 °C (8 hours at 45 °C), however optimum operation is within the +20
z
to +25 °C range.
Battery backup time is adversely affected by high and low temperatures. It is significantly reduced at
z
temperatures under 10 °C. Above 25 °C, battery service life is cut in half every 10 °C. Above 40 °C, battery
manufacturers no longer guarantee operation due to the risk of thermal runaway.
Air enters through the front and exits through the back.
z
60s
120s
11 kVA
63 A
160-280 Volts AC
7 Volts at nominal load
50/60 Hz (+/-10%)
3.75 kV / 5 M ohms
From 0° to +40 °C
95 %
Pn -10 % > 1000 m
444 x 131 x 635 mm
131 x 444 x 635 mm
86.5 kg
Configuration for
2 hours backup time
5 hours
7 hours
5. Appendices
t
Configuration for
4 hours backup time
12 hours
15 hours
Configuration for
8 hours backup time
20 hours
24 hours
34007558EN/AE - Page 37

Publicité

loading