27
UK
9 - DIP SWITCH DIP1
The settings are stored during the rest phase (gate closed).
The default settings are highlighted in the boxes with grey background.
DIP
Function
AUTOMATIC
1_1
STEP-BY-STEP
WITH STOP
TERMINAL 21
AS EDGE
1_2
TERMINAL 21
AS STOP
1_3
ANTI CRUSHING
1_4
SENSITIVITY
TOTAL
1_5
AUTOMATIC
RECLOSURE
AUTOMATIC
1_6
PEDESTRIAN
RECLOSURE
Status
Operation in response to the START command:
ŸGate closed
ŸDuring opening
ON
ŸGate open
ŸDuring closing
Operation in response to the START command:
ŸGate closed
ŸDuring opening
OFF
ŸGate open
ŸDuring closing
ŸAfter a STOP
Operation
:
Ÿ
Gate closed
ŸDuring opening
ON
ŸGate open
ŸDuring closing
Operation :
Ÿ Gate closed
ŸDuring opening
OFF
ŸGate open
ŸDuring closing
ŸAfter a STOP
OFF
Very High sensitivity.
OFF
OFF
High sensitivity.
ON
ON
Medium sensitivity.
OFF
ON
Low sensitivity.
ON
OFF
Total automatic reclosure disabled.
Enable the automatic closure or after the pause time set by default 20s
ON
or after the pause time learned.
Automatic pedestrian reclosure disabled.
OFF
Enable the automatic closure or after the pause time set by default 10s
ON
or after the pause time learned.
Description
→
OPENS
→
UNINFLUENTIAL
→
Reloads the automatic closing time if automatic closing
is enabled, otherwise it closes.
→
OPENS
→
OPENS
→
STOPS
→
CLOSES
→
STOPS
→
Inverts the motion
→
UNINFLUENTIAL
→
Immediate motion inversion for 1s at low speed,.
→
UNINFLUENTIAL
→
Immediate motion inversion for 1s at low speed.
→
UNINFLUENTIAL
→
STOP
→
STOP, no automatic reclosing
→
STOP
→
Reverses the motion
BE24G