• Coupling size of brazed pipe
External size
K
Standard outer dia. of
connected copper pipe
6.35
9.52
12.70
15.88
19.05
22.22
28.58
34.92
Selection of pipe materials and size
• Selection of pipe material
Material: Phosphorus deoxidation seam-less pipe
• Capacity code of indoor and outdoor units
• For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
• The capacity codes of the outdoor units are decided at each capacity rank. The maximum No. of connectable
indoor unit and the total value of capacity codes of the indoor units are also decided. (Table 2)
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable indoor
units differs based on the height difference between the indoor units.
• When height difference between the indoor units is below 15m: Up to 135% of capacity code (Equivalent to HP)
of the outdoor unit. (in case of MMY-MAP1202FT: 120% or less)
• When height difference between the indoor units is over 15m: Up to 105% of capacity code (Equivalent to HP) of
the outdoor unit.
Table 1
Capacity code
Indoo
r unit
Equivalent
capacity rank
to HP
007 type
0.8
009 type
1
012 type
1.25
015 type
1.7
018 type
2
024 type
2.5
027 type
3
030 type
3.2
036 type
4
048 type
5
056 type
6
072 type
8
096 type
10
Connected section
Internal size
G
External size
Internal size
Standard outer dia. (Allowable difference)
C
6.35 (±0.03)
9.52 (±0.03)
12.70 (±0.03)
12.81 (
15.88 (±0.03)
16.00 (
19.05 (±0.03)
19.19 (
22.22 (±0.03)
22.36 (
28.58 (±0.04)
28.75 (
34.90 (±0.04)
35.11 (
Table 2
Outdoor unit
Equivalent
model name
to capacity
2.2
MMY-MAP0802FT8
2.8
MMY-MAP1002FT8
3.6
MMY-MAP1202FT8
4.5
5.6
MMY-AP1602FT8
7.1
MMY-AP1802FT8
8
MMY-AP2002FT8
9
11.2
MMY-AP2402FT8
14
MMY-AP2602FT8
16
MMY-AP2802FT8
22.4
MMY-AP3002FT8
28
Connected section
Min. depth
of insertion
F
K
+0.04
6.45 (
)
7
–0.02
+0.04
9.62 (
)
8
–0.02
+0.04
)
9
–0.02
+0.04
)
9
–0.02
+0.03
)
11
–0.03
+0.03
)
11
–0.03
+0.06
)
13
–0.02
+0.04
)
14
–0.04
Capacity code
Equivalent
Equivalent
to HP
to capacity
8
10
12
16
18
20
24
26
28
30
10
Oval value
G
6
0.06 or less
7
0.08 or less
8
0.10 or less
8
0.13 or less
10
0.15 or less
10
0.16 or less
12
0.20 or less
13
0.25 or less
No. of
indoor units
22.4
13
28
16
33.5
16
45
27
50.4
30
56
33
68
40
73
43
78.5
47
84
48
(Unit: mm)
Min. thickness
of coupling
0.50
0.60
0.70
0.80
0.80
0.82
1.00
1.20
Capacity code
Equivalent to HP
Min.
Max.
5.6
10.8
7.0
13.5
8.4
14.4
11.2
21.6
12.6
24.3
14.0
27.0
16.8
32.4
18.2
35.1
19.6
37.8
21.0
40.5

Publicité