WIKA GDM-RC-100 Mode D'emploi page 10

Densimètre pour gaz avec chambre de référence
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3. Safety
3.9 Applicable standards and directives for installation, assembly, commissioning:
BGI 753 (SF₆ plants and equipment in Germany)
IEC 61634 (Handling of SF₆ gas)
IEC 60376 (New SF₆ gas, technical grade SF₆ gas)
EN
IEC 60480 (Used SF₆ gas)
CIGRE report 276, 2005 (Practical SF₆ gas handling instructions)
Leaks during operation:
IEC 60376 (New SF₆ gas, technical grade SF₆ gas)
IEC 60480 (Used SF₆ gas)
CIGRE 2002 ("SF₆ gas in the electrical industry")
3.10
Labelling, safety marks
Product label (example)
Model designation
Position and number of switch points
Measuring range
Permissible ambient temperature
Electrical characteristics
Article number
Date of manufacture
IP class
10
SF
is a colourless and odourless, chemically neutral, inert and non-flamma-
6
ble gas which is approx. five times heavier than air, non-toxic and not harmful
to the ozone layer.
Detailed information is given in IEC 60376 and IEC 61634.
Gas Density Monitor GDM-RC-100
S1: 0.61 MPa @ 20 ℃ SF6 , Falling
S2: 0.55 MPa @ 20 ℃ SF6 , Falling
S3: 0.55 MPa @ 20 ℃ SF6 , Falling
S4: 0.67 MPa @ 20 ℃ SF6 , Rising
RANGE: -0.1 ... 1.15 MPa @ 20 ℃ SF6
T
: -40...70 ℃ @ max. 5 A
a
>70...80 ℃ @ max. 1 A
12...250 V AC (50...60Hz) / DC
max. 5 A @ 250 V AC / 30 V DC
max. 0.25 A @ 250 V DC
Product/E- No.: 64408712
WIKA Alexander Wiegand SE & Co. KG
63911 Klingenberg
Before mounting and commissioning the instrument, ensure you read
the operating instructions!
11/19 IP65
WIKA operating instructions, model GDM-RC-100