12 – Specifi cations
12-1 UPS System Technical Specifi cations
Input
Input Voltage
Voltage Regulation
Harmonic Distortion
PFC (Full Load)
Frequency
Frequency Tolerance
Output
Output Voltage
Output Frequency
Total Harmonic (Linear Load)
Voltage Regulation
Frequency Regulation
Overload
Audible Warning
Battery Backup
UPS Abnormal
Display
LED
LCD
Interface
Standard
Optional
Others
Parallel Redundancy
EPO
SRAM Event Log
Parameter Configuration
Hot Standby Installation
Battery Temperature Compensation
Battery Cold-Start
Overall
Efficiency
Transfer Time
Temperature
Humidity (non-condensing)
Noise (1 m)
Dimensions (Power Module)
Weight (Power Module)
* With internal batteries.
12-2 UPS System Floor Loading Table
Model
SU20KX
Weight
267 kg
Floor Loading
600 kg/m
200706017 93-2688 SU manual 4C.indd 51
200706017 93-2688 SU manual 4C.indd 51
Model
(Capacity)
Static
Dynamic
Interior Oscillator
Synchronized
Normal
ECO
Width
Depth
Height
SU40KX
SU60KX
SU80KX
412 kg
210 kg
244 kg
2
927 kg/m
2
475 kg/m
2
552 kg/m
SU20KX
SU40KX
(20kVA/16kW)
(40kVA/32kW)
220/380V, 230/400V or 240/415V AC, 3O, 4-wire + ground, wye
-25% ~ +20%
< 5% (Full Load)
> 0.99
50 / 60 Hz
45 ~ 65 Hz
220/380V, 230/400V or 240/415V AC, 3O, 4-wire + ground, wye
50 / 60 Hz
≤3%
±1%
±7% (10% ~ 90% Linear Load)
±0.05 Hz
±5%
≤125% : 10 minutes; ≤150% : 1 minute
Intermittent
Continuous
UPS Status: Normal • Bypass • Backup • Fault
Input/Output • Bypass • Inverter • Frequency • Loading • Battery Voltage
UPS abnormal messages with intelligent self-diagnosis.
RS-232, Dry Contact
SNMPWEBCARD
Yes (1+1 for 2 UPS systems of the same type and capacity only.)
Standard (Local and Remote)
500 Records
Yes
Optional
Optional
Standard
94%
97%
0 ms
32° F ~ 104° F (0° C ~ 40° C)
90%
65 dBA
68 dBA
520 mm
850 mm
1165 mm
267 kg*
412 kg*
12-3 Battery Pack Floor Loading Table
BP480V26B
(40 12V batteries;
Model
26AH each)
2
Weight
Floor Loading
1064 kg/m
51
SU60KX
SU80KX
(60kVA/48kW)
(80kVA/64kW)
70 dBA
70 dBA
210 kg
244 kg
BP480V40C
(40 12V batteries;
40AH each)
470 kg
700 kg
2
1575 kg/m
2
11/29/2007 2:03:05 PM
11/29/2007 2:03:05 PM
1
2
3
4
5
6
7
8
9
10
11
12
13
14

Publicité

loading

Ce manuel est également adapté pour:

Smartonline su40kxSmartonline su60kxSmartonline su80kx