Télécharger Imprimer la page

Tripp-Lite SmartOnline SU20KX Manuel Du Propriétaire page 50

Publicité

Les langues disponibles

Les langues disponibles

11 – Communications
1
11-10 RS-232 Serial Port Circuit Diagram
The RS-232 DB9 serial port connects the UPS system to a workstation
2
or server (cable included). By communicating with the UPS system
through this port, Tripp Lite's PowerAlert UPS management software
(included) can monitor and control the UPS system. PowerAlert also
serves as an SNMP proxy allowing the UPS system to appear as an
SNMP-manageable device on the network.
3
RS-232 signals and operations include: load level, battery status, battery
level, operation mode, AC input voltage, AC output voltage, AC input
frequency, internal temperature, set shut-down delay time, enable/
disable alarm and remote shutdown.
4
Hardware
Baud Rate: 2400 BPS
Data Length: 8 bits
Stop Bit: 1 bit
Parity: NONE
5
Pin Assignment
Pin 2: TXD (Transmit Data)
Pin 3: RXD (Receive Data)
Pin 5: GND (Signal Ground)
6
11-11 Parallel Redundancy Port
The parallel redundancy port allows the UPS system to be connected to another UPS system of identical type and capacity for use in a parallel
redundancy (1+1) configuration for increased capacity or increased fault-tolerance. Warning: Use only the parallel redundancy cable that is
7
included with the UPS system. Attempting to use an incompatible cable may damage the UPS systems and create a serious risk of personal
injury and property damage.
8
9
10
11
12
13
14
200706017 93-2688 SU manual 4C.indd 50
200706017 93-2688 SU manual 4C.indd 50
(continued)
50
11/29/2007 2:03:04 PM
11/29/2007 2:03:04 PM

Publicité

loading

Ce manuel est également adapté pour:

Smartonline su40kxSmartonline su60kxSmartonline su80kx