6 – Internal Battery Connection
6-2 Internal Battery Connection Procedure
•
Place the UPS system in bypass (or turn it completely off) and turn
1
off the internal battery circuit breaker switch, located on the rear of
the UPS system.
•
Remove the battery access bezels, located on the front of the UPS
2
system.
•
3
Remove the battery cartridge fuses from each fuse block.
•
Disconnect the blue and white jumper cables attached to each fuse
4
block. Warning: When disconnecting the jumper cables, pull
them straight away from the fuse block with even force. Do not
wiggle them side-to-side, as this may damage the connector.
•
Remove the fuse block bracket. Note its orientation before
5
removal.