Installation and start-up of KEOR HPE UPS 200-250-300 kVA
Installation et démarrage de l'ASI KEOR HPE 200-250-300 kVA
Installazione e avviamento KEOR HPE UPS 200-250-300 kVA
The UPS must be so installed as to ensure its serviceability and to allow a correct air flow as much
as possible.
With regard to the minimum distances from the walls, for all of the UPS sizes the same installation
conditions apply as indicated in the table below.
Recommended clearances
Minimum clearances
The table below shows the air volume required for an optimal ventilation and cooling of the UPS.
Power (kVA)
Air volume (m
3
/h)
A (mm)
B (mm)
50
1200
0
1200
200
250
1800
2200
C (mm)
D (mm)
50
600
0
400
300
2300
OMP06262 REV. E
25