For a description of the UPS status in each of the failure conditions listed above, please refer to
the "Faults and alarms" section.
A28 CRITICAL STOP
NOTE: Reccomended to performe the service test before restart the UPS.
The UPS is equipped with internal protections which block the system.
Before to reset the alarm, must be sure that there are not critical fault on the UPS.
To reset this alarm, is required to performe "RESET ALARMS" procedure as
indicated above and restart completely the UPS.
5.3.2 Setting the battery
In case the UPS has been tested without knowing the characteristic data of the storage battery,
the BATTERY PARAM section allows to set such data. Each single settable parameter can be
accessed via the following page.
Picture 20 – Battery parameters setting
The various parameters setting pages are similar to each other and requires the operator to
enter and confirm the value; the setting page of the battery capacity is given below as a
reference.
34
OMP06263 REV. D
UPS user manual
Manuel de l'utilisateur de l'ASI