Télécharger Imprimer la page

LEGRAND KEOR HPE 200 kVA Manuel De Fonctionnement page 216

Publicité

Les langues disponibles

Les langues disponibles

Alarm
A13
Description
The inverter voltage or frequency are out of tolerance.
Possible
 Inverter shutdown due to an alarm.
causes
 Inverter failure.
Solutions
1. Check which alarms are present and carry out the indicated
2. If the alarm persists, contact our Technical Support Service.
Alarm
A14
Description
The phase rotation of the bypass line is wrong.
Possible
 Wrong connection of power cables.
causes
Solutions
1. Check the phase rotation.
2. If the alarm persists, contact our Technical Support Service.
Alarm
A15
Description
The voltage or frequency of the bypass line are out of tolerance.
Possible
 Bypass line instability or failure.
causes
 Wrong phase rotation.
Solutions
1. Check the connections to the mains.
2. Check the stability of mains voltage.
3. If the alarm persists, contact our Technical Support Service.
Alarm
A16
Description
The load is fed by the bypass line.
Possible
 Temporary changeover due to inverter failure.
causes
Solutions
1. Verify the inverter status and check whether other alarms are
2. If the alarm persists, contact our Technical Support Service.
Manuel de l'utilisateur de l'ASI
INVERTER OUT OF TOLERANCE
procedures.
BYPASS WRONG SEQUENCE
BYPASS FAULT
BYPASS --> LOAD
present.
UPS user manual
Utilizzo dell'UPS
OMP06263 REV. D
55

Publicité

loading

Ce manuel est également adapté pour:

Keor hpe 300 kvaKeor hpe 80kw960572