Instructions d'utilisation et d'entretien – v4.2.2
FONCTIONNALITÉ
POUR TOUS LES CAS
REPRISE DES FONC-
TIONNALITÉS SETUP ET
CONTRÔLE PAR L'INTER-
FACE UTILISATEUR.
DM4.0.0 | TACTOUCH:2.44
SI MODE DE FONCTIONNEMENT LS
ARRÊT DES VENTILATEURS
POUR UNE VALEUR DE
SIGNAL 0-10V
DM4.0.0 | TACTOUCH:2.44
ARRÊT DES VENTILATEURS
POUR UNE VALEUR DE
SIGNAL 0-10V
DM4.0.0 | TACTOUCH:2.44
ARRÊT DES VENTILATEURS
POUR UNE VALEUR DE
SIGNAL 0-10V
DM4.0.0 | TACTOUCH:2.44
ARRÊT DES VENTILATEURS
POUR UNE VALEUR DE
SIGNAL 0-10V
DM4.0.0 | TACTOUCH:2.44
2ÈME SIGNAL 0-10V
CONNECTÉ SUR K3
DM4.0.0 | TACTOUCH:2.44
2ÈME SIGNAL 0-10V
CONNECTÉ SUR K3
DM4.0.0 | TACTOUCH:2.44
54
DESCRIPTIF
SI LES FONCTIONNALITÉS DE SETUP ET
DE CONTRÔLE ONT ÉTÉ FAITES PRÉ-
ALABLEMENT VIA COMMUNICATION
MODBUS, WI-FI, KNX, ETHERNET, POSSI-
BILITÉ DE RENDRE CES FONCTIONNALI-
TÉS À L'INTERFACE.
POSSIBILITÉ D'ARRÊTER LES VENTILA-
TEURS AUTOMATIQUEMENT SI LE SIGNAL
0-10V EST INFÉRIEUR À VINF
CONFIGURATION DE LA VALEUR DE VINF
POSSIBILITÉ D'ARRÊTER LES VENTILA-
TEURS AUTOMATIQUEMENT SI LE SIGNAL
0-10V EST SUPÉRIEUR À VSUP
CONFIGURATION DE LA VALEUR DE VSUP 7.1
POSSIBILITÉ DE PILOTER LE DÉBIT DES
VENTILATEURS DE PULSION VIA UN
SIGNAL 0-10V RACCORDÉ SUR L'ENTRÉE
K2 ET LES VENTILATEURS D'EXTRACTION
VIA UN AUTRE SIGNAL 0-10V RACCORDÉ
SUR L'ENTRÉE K3. LE LIEN DÉBIT – SI-
GNAL DOIT ÊTRE LE MÊME.
LORSQU'UN 2ÈME SIGNAL 0-10V EST
CONNECTÉ SUR K3, SÉLECTIONNER LE
FLUX D'AIR QU'IL CONTRÔLERA :
-
EXTRACTION (PAR DÉFAUT):
POSSIBILITÉ DE PILOTER SÉPARÉMENT LES
FLUX DE PULSION ET EXTRACTION. LE
FLUX DE PULSION VIA LE SIGNAL 0-10V
CONNECTÉ SUR K2, ET LE FLUX D'EX-
TRACTION VIA UN AUTRE SIGNAL 0-10V
CONNECTÉ SUR K3. LE LIEN ENTRE LA
VALEUR DU SIGNAL ET LE DÉBIT CORRES-
PONDANT DOIT ÊTRE LE MÊME.
-
PULSION : LE SIGNAL CONSIDÉ-
RÉ POUR LE LIEN LS SERA LE MAXIMUM
ENTRE LA TENSION SUR K2 PROVENANT
DU PREMIER SENSEUR ET LA TENSION
SUR K3 PROVENANT DU SECOND SEN-
SEUR.
LE DÉBIT D'EXTRACTION SERA DONNÉ
PAR LE RATIO %EXT/PUL.
TAC5 DM
ETAPE
TEXTE SUR
L'ÉCRAN
4
CONTRÔLE
REPRISE CONTRÔLE PAR
PAR RC ? O
TACTOUCH
5 / 6
ARRET VENT
ARRÊT VENTILATEUR VIA
SI
0-10V/ARRÊT VENTILATEUR
V<VINF? N
0-10V < VINF
6.1
VINF :
ARRÊT VENTILATEUR VIA
00,0 V
0-10V/ VINF
7
V>VSUP?
ARRÊT VENTILATEUR VIA
N
0-10V/ARRÊT VENTILATEUR
0-10V > VSUP
VSUP :
ARRÊT VENTILATEUR VIA
10,0 V
0-10V/ VSUP
8
0-10V
2ÈME SIGNAL 0-10V/ ACTIVA-
SUR K3? N
TION DU 2ÈME 0-10V
8.1
FLUX ?
2ÈME SIGNAL 0-10V/FLUX
EXTRACT.
CONTRÔLÉ PAR 2EME 0-10V
Instructions d'utilisation et d'entretien – v4.2.2
TAC5 DM + TACTOUCH