Installation Of Kwl 60 Dr Compensation Ring; Functional Description To Menu Tree; Comfort Controller Kwl 60 Bc - Helios EcoVent KWL EC 60 PRO Notice De Montage Et D'utilisation

Masquer les pouces Voir aussi pour EcoVent KWL EC 60 PRO:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Instructions
UK
CHAPTER 4
COMFORT CONTROLLER
KWL-BCU/KWL-BCA
Wall installed unit KWL EC 60 Pro / ... Pro FF
3.4

Installation of KWL 60 DR compensation ring

attach extension
sleeve to wall sleeve
attach partition elements
to the extension sleeve
4.0
Functional description to menu tree of comfort controller KWL-BC..
A1 = Initial start-up:
The following queries are carried
out at initial start-up:
1.) Controller address: In case that
only one controller is connected,
address 1 can be used. If several
controllers (max. 4) should be
connected, each controller must
be assigned to an address of its
own (see point D8).
2.) Language: Selection: German,
English, French or Italian (see
point D8).
3.) Date and time: Setting of the
current date and time (see point
D9).
Master / Slave – Mode:
Via Dip-switch 1 – on/off (see wiring
diagram SS-950), a KWL-unit can be
defined as a Master- or Slave unit. It
is to be noted that in the network only
one Master-unit is defined. The
remaining KWL-units must be defi-
ned as Slave-units, which are then
subordinated to the Master automati-
cally.
Thus one or more KWL-units (max.
10, see wiring diagram SS-958) can
be operated via the control system.
B5-B14 = Auto / Manual – Mode:
The speed control of the KWL-unit is
carried out by an automatic or
manual power control. In the auto-
matic mode the speed control takes
place in dependence of the room
humidity,
the
CO
-concentration
2
and/or the weekly program. For this
accessory components like CO
sensor respectively humidity sensor
must the connected.
In the manual mode the speed con-
trol is carried out individually. By tur-
ning of the rotating encoder knob the
following levels can be selected:
Level 0-1-2-3-4-intake air-extract air.
Attach extension of
condensate drain
fasten compensation
ring to external wall
(fastening screws
from stainless steel
not provided by Helios)
If the CO
-concentration rises over
2
1600 ppm or the humidity value is
over 80 % relative humidity, an infor-
mation "humidity alarm" or "CO
alarm" appears, i.e. the selected
speed step is insufficient.
C1 = Booster mode:
After activating the booster mode,
the KWL EC Pro operates in the pre-
set speed step. The remaining runti-
me in the booster mode is shown in
the display and can be deactivated at
any time. Over submenu D3 (boo-
ster), speed step and booster runti-
me (1 - 180 minutes) can be set indi-
vidually.
C2 = Whisper mode:
After activating the whisper mode,
the KWL EC Pro operates in the pre-
set speed step. The remaining runti-
me in the whisper mode is shown in
the display and can be deactivated at
any time. Over submenu D4 (whisper
mode), speed step and booster run-
time (1 - 180 minutes) can be set
individually.
C4 = Clock timer:
It is possible to select between 6
already preset weekly programs: WP
1, WP 2, WP 3, WP 4, WP 5, WP
OFF. Select and confirm the desired
WP in the submenu C4.1 (standard
weekly program) for this purpose. If
an individual weekly program is to be
created, this can be specified in the
submenu 4.2 (individual weekly pro-
gram) for each weekday.
-
2
C5 = Vacation program:
For example a firm vacation date can
be deposited over the menu vacation
program. For this time duration an
individual ventilation process can be
set. At the beginning of the vacation
it starts automatically and switches
off again independently. The result is
an ideal ventilation of your property
during this time.
4
fig.10
cut extension sleeve and
partition element flush
with compensation ring
compensation ring
cut condensate drain
SS-932
to 20 mm excess
length to wall
C6 = Sensor values:
A humidity sensor is factory-installed
in the unit. The humidity values are
-
manually adjustable and are display-
2
ed in the graphic display of the con-
troller.
Furthermore, up to four CO
(accessories:
KEL-CO
9988) for detection of the CO
centration in the indoor air can be
connected and displayed.
C7 = Settings:
Over the setup menu several para-
meters can be adjusted individually.
D1 = Humidity control:
The most important functions are
defined in the submenu D1.
If the humidity control is activated,
the ventilation control takes place as
a function of the relative humidity,
which is measured directly in the
extract air. Following individual set-
tings are possible:
Setpoint: Setting of relative humidity
for level 1.
Switching steps: Switching threshold
in next level run on time: If the set-
point is not reached within 2 hours, a
mandatory pause takes place from 0
to 24 hours, in order to prevent a
continuous running.
D6=Supply and extract air level:
The supply and extract air level can
be set individually.
D7 = Filter change:
The interval for changing the filter can
be set between 2 till 9 months. The
remaining period for a filter change
can be displayed by a query. With an
earlier filter change, the remaining
period must be reset.
-sensors
2
,
Ref.No.
2
con-
2