Télécharger Imprimer la page

JUMO iTRON B 70 2040 Serie Notice De Mise En Service page 30

Régulateur compact géré par microprocesseur

Publicité

Les langues disponibles

Les langues disponibles

Programming example
After the start via the logic input or from the keys, the process has to be controlled for 30 min-
utes to a setpoint of 80°C. The control action is to be cancelled in the event of a power failure.
Configuration:
- C111— C116: Controller programming
- C117=5: Logic input = timer control
- C120=1: Timer function = time-limited control
- C121=6: Start condition for timer = via logic input/keys - cancellation on power failure
- C122=0: Timer signalling = no function
- C123=1: Time unit (timer) = mm.ss
Operation:
h Enter the setpoint SP (80°C)
h Press the
q
key until t
0
is indicated
i
h Change over to the timer level using
q
(at least 2sec)
h Enter the timer start value t
0 _ (30.00)
i
h Return to the operating level (timer value) with
q
h Start the control action via the logic input or with
i
30

Publicité

loading