5. Commissioning, operation
5.4.2.7 Status register
Address
Register
00200
00201
00201
00202
00202
00203
00203
00204
00204
00205
00221
00222
After a restart (voltage supply was interrupted), the error memory is reset. Writing 0x0001 in
register address 00201 has the same effect.
Description of the error memory
Bit
Description
0
Pressure signal below the lower limit value (< 0 bar)
1
Pressure signal above the upper limit value (> 16 bar)
2
Pressure sensor failure
3
Temperature signal below the lower limit value (< -40 °C [-40 °F])
4
Temperature signal above the upper limit value (> 80 °C [176 °F])
Communication error pressure/ temperature sensor
5
6
Gas density below the lower limit value (liquefaction of SF
7
Gas density above the upper limit value (> 80 g/l)
8
Failure of the humidity sensor (only model GDHT-20)
9
Communication error of humidity sensor (only model GDHT-20)
10
Recurring Modbus
11
Inadmissible mixing ratio, sum of all gas proportions ≠ 100 %
Example: 0x0082
Bit 1 and 7 are set. The upper limit values for pressure and gas density are exceeded.
Software reset
Writing 0x0001 in register 202 causes a software reset. After this process all changed
parameters take effect (e.g. change of address).
WIKA operating instructions transmitter, models GDT-20 and GDHT-20
Function
Error memory
Error memory reset
Software reset
Resetting to standard
Start heating
process (only model
GDHT-20)
Manual definiti-
on of the heating
interval (only model
GDHT-20)
communication error
®
Value definition,
Writable
triggering the
function
16 bit (see the
Read only
following table)
Writing 0x0001
Yes
Writing 0x0001
Yes
Writing 0x0001
Writing 0x0001
Writing minutes
gas)
6
EN
Yes
Yes
Yes
43