SCROLLING HELP TEXT
Process Value (»Normal«): xxxx
SE.BR --> SENSOR WIRE BREAKAGE
SE.SH --> SENSOR SHORT CIRCUIT
IN.HI
--> INPUT OVERRANGE
IN.LO
--> INPUT UNDERRANGE
9.9.9.9 --> DISPLAY OVERRANGE
-1.9.9.9 --> DISPLAY UNDERRANGE
HW.ER --> HARDWARE ERROR
EE.ER --> EEPROM MEMORY ERROR
RA.ER --> RAM MEMORY ERROR
CJ.ER --> CJC SENSOR ERROR
NO.CA --> DEVICE NOT CALIBRATED
FastSet (set enabled):
REL1
xxxx
--> SETPOINT RELAY 1 - PRESS OK TO SAVE
REL2
xxxx
--> SETPOINT RELAY 2 - PRESS OK TO SAVE
FastSet (set disabled):
REL1
xxxx
--> SETPOINT RELAY 1 - READ ONLY
REL2
xxxx
--> SETPOINT RELAY 2 - READ ONLY
Configuration Setup:
PASS
xxxx
--> SET PASSWORD
IN
POTM --> POTENTIOMETER INPUT
CURR --> CURRENT INPUT
VOLT
--> VOLTAGE INPUT
TEMP --> TEMPERATURE SENSOR INPUT
RANG
(when volt selected)
2-10
--> INPUT RANGE IN VOLTS
0-10
--> INPUT RANGE IN VOLTS
0.2-1
--> INPUT RANGE IN VOLTS
0.0-1
--> INPUT RANGE IN VOLTS
DEC.P
1111
--> DECIMAL POINT POSITION
111.1
--> DECIMAL POINT POSITION
11.11
--> DECIMAL POINT POSITION
1.111
--> DECIMAL POINT POSITION
DI.LO
xxxx
--> DISPLAY READOUT LO W
DI.HI
-->
xxxx
--> DISPLAY READOUT HIGH
REL.U
PERC --> SET RELAY IN PERCENTAGE
DISP
--> SET RELAY IN DISPLAY UNITS
REL1
xxxx
--> SETPOINT RELAY 1
ACT1
INCR
--> ACTIVATE AT INCREASING SIGNAL
DECR --> ACTIVATE AT DECREASING SIGNAL
HYS1
xxxx
--> HYSTERESIS RELAY 1
ERR1
HOLD --> HOLD RELAY AT ERROR
ACTI
--> ACTIVATE RELAY AT ERROR
DEAC --> DEACTIVATE RELAY AT ERROR
NONE --> UNDEFINED STATUS AT ERROR
REL2
xxxx
--> SETPOINT RELAY 2
38
All manuals and user guides at all-guides.com
ACT2
INCR
--> ACTIVATE AT INCREASING SIGNAL
DECR --> ACTIVATE AT DECREASING SIGNAL
HYS2
xxxx
--> HYSTERESIS RELAY 2
ERR2
HOLD --> HOLD RELAY AT ERROR
ACTI
--> ACTIVATE RELAY AT ERROR
DEAC --> DEACTIVATE RELAY AT ERROR
NONE --> UNDEFINED STATUS AT ERROR
A.OUT
20-4
--> OUTPUT RANGE IN mA
20-0
--> OUTPUT RANGE IN mA
4-20
--> OUTPUT RANGE IN mA
0-20
--> OUTPUT RANGE IN mA
O.LO
xxxx
--> DISPLAY VALUE FOR OUTPUT LOW
O.HI
xxxx
--> DISPLAY VALUE FOR OUTPUT HIGH
O.ERR
23mA --> NAMUR NE43 UPSCALE AT ERROR
3,5mA --> NAMUR NE43 DOWNSCALE AT ERROR
0mA
--> DOWNSCALE AT ERROR
NONE --> UNDEFINED OUTPUT AT ERROR
E.PAS
NO
--> ENABLE PASSWORD PROTECTION
YES
--> ENABLE PASSWORD PROTECTION
N.PAS
xxxx
--> SELECT NEW PASSWORD
RANG
(when current selected)
4-20
--> INPUT RANGE IN mA
0-20
--> INPUT RANGE IN mA
CA.LO
YES
--> CALIBRATE POTENTIOMETER LOW
NO
--> CALIBRATE POTENTIOMETER LOW
CA.HI
YES
--> CALIBRATE POTENTIOMETER HIGH
NO
--> CALIBRATE POTENTIOMETER HIGH
UNIT
°F
FAHRENHEIT
°C
CELSIUS
TYPE
TC.W5 --> TC TYPE W5
TC.W3 --> TC TYPE W3
TC. U --> TC TYPE U
TC. T
--> TC TYPE T
TC. S
--> TC TYPE S
TC. R
--> TC TYPE R
TC. N --> TC TYPE N
TC. L
--> TC TYPE L
TC. K
--> TC TYPE K
TC. J
--> TC TYPE J
TC. E
--> TC TYPE E
TC. B
--> TC TYPE B
PT.4W --> PT-100 4-WIRE
PT.3W --> PT-100 3-WIRE
PT.2W --> PT-100 2-WIRE
DEC.P
(when temp selected)
1111
--> DECIMAL POINT POSITION
111.1
--> DECIMAL POINT POSITION
CONFIGURATION / OPERATING THE
FUNCTION KEYS
Documentation for routing diagram.
In general:
When configuring the display you are guided through all parameters, you can
choose the settings which fit the application. For each menu there is a scrol-
ling help text which is automatically shown in the display, this starts after 5
seconds if no key has been activated.
Configuration is carried out by using the 3 function keys.
will increase the numerical value or choose the next parameter.
will decrease the numerical value or choose the previous parameter.
will accept the chosen value and end the menu.
If a function does not exist in the display all parameters are skipped to make
the configuration as simple as possible.
Once the configuration has been entered the display will show "----".
Pressing and holding
will return to the previous menu or return to the default
state (1.0) without saving the changed values or parameters.
If no key is activated for 2 minutes, the display will return to the default state
(1.0) without saving the changed values or parameters.
Further explanations:
Fast setpoint adjustment and relay test: These menus allow you to change
the set point quickly and to check the operation of the relays.
Pressing
and
at the same time will change the state of the relay – this change
is indicated by the diodes on the display. Pressing
change.
Holding down
for more than 0.5 seconds will return the unit to the default
state without changing the set point.
Password protection:
Using a password will stop access to the menu and parameters. There are two
levels of password protection. Passwords between 0000...4999 allow access
to the fast set point adjustment and relay test. (Using this password stops
access to all other parts of the menu). Passwords between 5000...9999 stop
access to all parts of the menu, fast set point and relay test. (Current set
point is still shown). By using the master password 2008, all configuration
menus are available.
will save the set point
39