Current outout:
Signal range (span) ...................................... 0...20 mA
Programmable signal ranges ...................... 0...20 / 4...20 /
Load (max.) .................................................. 20 mA / 800 Ω / 16 VDC
Load stability ............................................... ≤ 0.01% of span / 100 Ω
Sensor error detection ................................ 0 / 3.5 / 23 mA / none
NAMUR NE 43 Upscale .............................. 23 mA
NAMUR NE 43 Downscale .......................... 3.5 mA
Current limit ................................................. ≤ 28 mA
Relay outputs:
Hysteresis, min ............................................ 0.1°C / °F or 0.1% of span / 1 count
Hysteresis, max ........................................... 25% of span
Max. voltage ................................................ 250 VRMS
Max. current ................................................ 2 A / AC
Max. AC power ........................................... 500 VA
Max. current at 24 VDC .............................. 1 A
Sensor error detection ................................ Make / Break / Hold / None
UL installation requirement:
For use on a flat surface of a Type 1 enclosure
Use 60/75°C cobber conducters only
Max. ambient temperature .......................... 60°C
Max. wire size, pins 41...46 ......................... AWG 30-16
Max. wire size, others ................................. AWG 30-12
UL file number ............................................. E248256
Marine approval:
Det Norske Veritas, Ships & Offshore ......... Standard for Certification No. 2.4
Observed authority requirements:
EMC 2004/108/EC
Emission and immunity ......................... EN 61326
LVD 73/23/EEC ............................................ EN 61010-1
UL, Standard for Safety .............................. UL 508
Sensor error detection / sensor error detection outside range:
Sensor error check in 5714 variants
Variant:
Configuration
5714A
Always:
ERR1=NONE, ERR2=NONE:
5714B
else:
O.ERR=NONE:
5714C
else:
ERR1=NONE, ERR2=NONE, O.ERR=NONE:
5714D
else:
32
All manuals and user guides at all-guides.com
20...0 / 20...4 mA
Standard:
Sensor error detection:
ON
OFF
ON
OFF
ON
OFF
ON
Outside range readout (IN.LO, IN.HI):
If the valid range of the A/D converter or the polynomial is exceeded
Input
Range
0..1 V / 0.2..1 V
VOLT
0..10 V / 2..10 V
CURR
0..20 mA / 4..20 mA
POTM
-
TEMP
TC / Pt100
Sensor error detection (SE.BR, SE.SH):
Input
Range
CURR
Loop break (4..20mA)
TC
Pt100 2-wire
TEMP
Pt100 3-wire
Pt100 4-wire
Display readout below min. / above max. (-1.9.9.9, 9.9.9.9):
Input
Range
CURR
All
VOLT
All
POTM
-
Readout at hardware error
Error search
Test of internal communication uC / ADC
Test of internal CJC sensor
Check-sum test of the configuration in RAM
Check-sum test of the configuration in EEPROM
! Error indications in the display blink once a second. The help text explains the error.
Readout
Limit
IN.LO
< -25 mV
IN.HI
> 1.2 V
IN.LO
< -25 mV
IN.HI
> 12 V
IN.LO
< -1.05 mA
IN.HI
> 25.05 mA
IN.LO
< -0.5%
IN.HI
> 100.5%
IN.LO
< temperature range
IN.HI
> temperature range
Readout
Limit
SE.BR
<= 3.6 mA; > = 21 mA
SE.BR
> ca. 750 kohm / (1,25V)
SE.BR
> ca. 15 kohm
SE.SH
< ca. 15 ohm
SE.BR
> ca. 15 kohm
SE.SH
< ca. 15 ohm
SE.BR
> ca. 15 kohm
SE.SH
< ca. 15 ohm
Readout
Limit
-1.9.9.9
Display readout <-1999
9.9.9.9
Display readout >9999
-1.9.9.9
Display readout <-1999
9.9.9.9
Display readout >9999
-1.9.9.9
Display readout <-1999
9.9.9.9
Display readout >9999
Readout
Error cause
HW.ER
Permanent error in ADC
CJ.ER
CJC sensor defect
RA.ER
Error in RAM
EE.ER
Error in EEPROM