Technical Data; General Data; Electrical Data - Festo 8129208 Notice D'utilisation

Energy measurement box single-phase
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7 Technical data

7.1 General data

Parameter
Device operation
Dimensions
Weight
Subject to change

7.2 Electrical data

Parameter
Input voltage
Input frequency
Max. device power consumption
Total current (including connected loads)
Primary fuse
Protection class
Overvoltage category
Pollution degree
Electrical supply connection
Electrical connection, output
Output voltage
Output current
Short-circuit protection
Overload protection
Operating temperature range
Max. relative humidity
Degree of protection
Subject to change
© Festo Didactic 8130877
Single-Phase Energy Measurement Box – Operating Instructions
Value
For indoor use only up to 2000 m above sea level
312 x 312 x 256 mm
5.1 kg
Value
110 – 230 V ±10 % AC
50/60 Hz
108 W
Max. 10 A
T10L/250 V, micro fuse, 5x20 mm, 10 A, 250 V, slow-blow
1, operation with protective grounding
II, operation in building installations
2, laboratory environment
IEC panel plug type C14
3x IEC panel socket type C13
24 V DC
max. 4 A
Switch off the switched-mode power supply
Resettable device fuse (4 A)
5...40 °C/100 %
80 %
IP20
19