The control board does not work any more using
the transmitter, only with the switch and even then
only as long as a button is pressed and kept
pressed.
Open with push-button (1) or CLOSE with push-
button (2)
The unit does not close automatically, it
OPENS automatically
Control board does not work with transmitter
Gate can only be opened
The control board is not running
The wings do not open completely.
(Remote controlled) universal receiver does not work Observe polarity (terminals 15/16)
1.Dip switch setting not as desired
2.A safety photocell, a contact strip or the
stop disables the control board
3.Only one photocell was connected for
OPEN
The motor cables are not connected correctly
1.transmitter not programmed
2.An photocell blocks
1.photocell blocks
2.Dip switch setting not as desired
No covered distance learned
1.Insufficient force in the event of high
wind loads
(entire gates)
2.Gate sluggish/heavy
D e c l a r a t i o n o f C o n f o r m i t y
Automatic Gate Opener Models HC280ML, HC300ML/MLS, HC400ML/MLS,
HC600ML/MLS Series
are in conformity to the applicable
sections of StandardsEN300220-3 • EN55014 • EN61000-3 • EN60555, EN60335-1 • ETS
300 683 • EN60335-1: 2002 • EN60335-2-103: 2003 • EN55014-1: 2000 + A1 + A2 •
EN55014-2: 2001 • EN61000-3-2: 2000 • EN61000-3-3: 1995 + A1 • EN 301 489-3,
V1.3.1 • EN 300 220-3 V1.1.1 • EN 13241-1
per the provisions & all amendments
of the EU Directives ..................................................73/23/EEC, 89/336EEC, 1999/5/EG
D e c l a r a t i o n o f I n c o r p o r a t i o n
Automatic Gate Opener Models when installed and maintained according to all the
Manufacturer's instructions in combination with a Gate, which has also been installed and
maintained according to all the Manufacturer's instructions, meets the provisions of EU
Directive 89/392/EEC and all amendments.
I, the undersigned, hereby declare that the equipment
specified above and any accessory listed in the manual
B.P.Kelkhoff
Manager, Regulatory Affairs
Chamberlain GmbH
D-66793 Saarwellingen
Januar, 2006
© Chamberlain GmbH 2006, all rights reserved
conforms to the above Directives and Standard
1.Correction of the dip switch,
elimination of fault required. If the fault
cannot be repaired, it will be necessary
to "reset" and reprogram (see photocell)
2.At least one photocell must be
connected and activated for CLOSED
or OPEN & CLOSED.
The motor cables (brown,black) must be
swapped
1.Program transmitter
2.Check photocells
1.Function and connection must be
checked
2.Check dip switch
Learn covered distance.
See Initial operation
1.Reset force ( increase )
2.Improve ease of movement
3.Program control board again
Swap "+" and "-" cables
s.