12 – Specifications
1
12-1 UPS System Technical Specifications
2
Rating Voltage
Voltage Regulation
3
Input Current Harmonic Distortion (Full
Input
Load)
PFC (Full Load)
Frequency
Frequency Tolerance
4
Output Voltage
Output Frequency
Total Harmonic (Linear Load)
Voltage Regulation
5
Output
Frequency Regulation Interior Oscillator Hz
Overload
6
Battery Backup
Audible Warning
UPS Abnormal
LED
Display
LCD
7
Monitor
Remote
Control
Standard
8
Interface
Optional
Parallel Configuration
EPO
9
SRAM Event Log
Others
Parameter Configuration
Hot Standby Installation
Battery Temperature Compensation
Battery Cold Start
10
Efficiency (at full load)
Transfer Time
Operating Temperature
11
Humidity (Non-Condensing)
Overall
Noise (@ 1 m)
Dimension
12
Weight
12-2 UPS System Floor Loading Table
13
Model
Weight
Floor Loading
14
12-212-93-3141.indb 56
All manuals and user guides at all-guides.com
Capacity
Hz
Hz
Hz
Static
Dynamic
Synchronized
Normal
ECO
ms
°C
dBA
Width
mm
Depth
mm
Height
mm
Kg
SU120KX
379 kg
748 kg/m²
220/380, 230/400, 240/415
V
%
<70% Full Load: -48/+20 (at 230/400V); Full load: -25/+20 (230/400V)
%
V
220/380, 230/400, 240/415 (3Φ 4W+Earth)
%
%
%
7 (Max Deviation for 10% ~ 90% Linear Load)
%
≦125%: 10 minutes ; ≦150%: 1minute
UPS status: Normal, Bypass, Backup and Fault
Input/Output, Bypass, Inverter, Frequency, Loading and Battery voltage, current,
UPS abnormal message and intelligent self diagnostics
Monitor up to 31 PCs, Graphically display records and historical data and
Remote control the Inverter and alarm, setup password and auto-dial warning
RS232, Dry Contact Output/Input
SNMP card, Modbus card, Relay I/O control card, Environmental sensor box,
Up to 4 UPS systems of the same capacity for redundancy capacity
Standard (Local and Remote)
%
%
%
56
120KVA/96KW
(3Φ 4W+PE)
< 4
> 0.99
50 / 60
45 ~ 65
50 / 60
≦3
±1
±0.05
±5
Intermittent
Continuous
Fault records retrieved
SNMP+5 Ports Hub
Yes (500 records)
Yes
Feasible
Optional
Standard
94
97
0
0~40
90
≤70
520
975
1695
379
12/28/2012 11:18:16 AM