Télécharger Imprimer la page

Tripp-Lite SmartOnline SU120KX2 Manuel Du Propriétaire page 40

Publicité

Les langues disponibles

Les langues disponibles

10 – Display and Configuration
1
10-5-2 Output Setup
From the "FREQ CONVERTER MODE" screen, use the scroll
5
2
buttons ( , ) to select the desired setting and press the enter
button (
) to confirm the setting. In frequency converter mode,
the UPS will convert the incoming electrical power frequency
to a different output frequency. Therefore, 60Hz can change to
50Hz output or 50Hz input can change to 60Hz output. When
3
in frequency converter mode, bypass power is not an available
source (the UPS will not transfer to bypass).
4
5
Redundancy
6
Use " " or " " to select the desired number of modules for
6
redundancy (usually one) for redundancy, then press "
confirm.
This feature allows the user to determine an acceptable power
output limit to guarantee a redundancy of N+1. When this feature
is enabled, the UPS will send an alarm when power usage exceeds
7
80% of the "non-redundant" power modules while maintaining
the number of redundant power modules set. For example, on a
120kVA UPS, if a Redundancy Setup is set to "1 Power Module",
the UPS will trigger an alarm when you exceed 80% of 100kVA
as to guarantee one power module for N+1 redundancy.
8
Press "ESC" to return to the "UPS SETUP" menu.
9
10-5-3 Battery Setup
Use " " or " " to select "BATTERY", then press "
10
All parameters in this segment can only be changed when UPS is in "Bypass Mode".
11
12
13
14
12-212-93-3141.indb 40
All manuals and user guides at all-guides.com
(continued)
" to
" to confirm.
(continued)
5
6
40
12/28/2012 11:18:06 AM

Publicité

loading