8 – Start-Up, Shutdown and Bypass
1
8-11 Switching to Normal Mode from Manual Bypass Mode (Parallel UPS—MUS)
•
If the UPS systems have external battery cabinets connected,
1
2
switch on the external battery cabinet circuit breaker switch of
each battery cabinet for each UPS.
3
4
•
2
Switch on the bypass input circuit breaker switch
output circuit breaker switch
5
6
•
Confirm that all UPS systems are in manual bypass mode, then
3
switch off the manual bypass input circuit breaker switch
of each UPS system. The LCD screen will read "ON AUTO
BYPASS".
7
8
•
Switch on the main input circuit breaker switch
4
system.
9
10
•
Press the ON button
A
5
you hear a beep), then release the button. Press the ON button
for each of the remaining UPS system for 3 seconds (until you
hear a beep), then release the button. When the inverters of all
UPS systems are operating normally, they will switch to on-line
11
(normal) mode at the same time.
12
13
14