2-Hand control (switch 1 in position 5)
4 pairs of 2-hand buttons Typ III A or 2 pairs of 2-hand buttons Typ III C
according to DIN EN 574 can be connected in this function. The number
of connected button pairs has to be selected on the device.
K1 and K2 can only be activated, if 3 conditions are fulfilled:
- First all button pairs have to be in initial position.
- Both buttons of 1 pair have to be pressed within 0.5 sec.
- All connected pairs have to be operated within 15 s.
If changeover contacts are used in the 2-hand buttons the switchover time
has to be less then 50 ms. If it is longer the outputs K1 and K2 are switched
off and the unit gives failure code 7. This failure is stored and can only be
reset by disconnecting the auxiliary supply.
Function diagram
Auxiliary
voltage (A1/A2)
Button 1 S1 (S11/S12)
Button 1 S2 (S13/S14)
Button 2 S1 (S21/S22)
Button 2 S2 (S23/S24)
K1/K2 (13-14,
23-24, 33-34)
48 (no button activated)
58 (all buttons activated)
<0,5s
<15s
: off
: on
: flashing
Two-hand control, 2 pairs of buttons with 2 NO contacts each
Set-up instructions
The device has to be connected as shown in the application examples. When
connecting the push-buttons in parallel or in series the safe function of the
relay is disabled. The buttons must be designed and installed in a way, that
it is not possible to manipulate or to operate them without intention.
The distance between push buttons and dangerous area must be chosen
in a way that it is not possible to reach the dangerous area after release of
one button before the dangerous movement comes to standstill.
The safety distance "S" is calculated with the following formula:
S = V x T + C
a) moving speed of person V = 1 600 mm/s
b) stopping time of the machine T (s)
c) Additional safety distance C = 250 mm
If the risc of accessing the dangerous area is prohibited while the push
buttons are pressed e.g. by covering the buttons, C can be 0. The minimum
distance has to be in this case 100 mm. See also EN 574.
All manuals and user guides at all-guides.com
0,5s
15s
M8444
Settings on switch 10
Switch
Number of
10
button pairs
0
1
1
2
2
3
3
4
4
1
5
2
6
1
7
2
8
3
9
1
Terminal designation
Ter-
Pair of buttons with
minal
2 NO contacts each
2 C/O contacts each
S11
Pair 1, button S1
S12
S14
S13
Pair 1, button S2
S21
S22
Pair 2, button S1
S24
Pair 2, button S2
S23
S31
Pair 3, button S1
S32
S34
S33
Pair 3, button S2
S41
S42
Pair 4, button S1
S44
S43
Pair 4, button S2
Semiconductor outputs
Output
Flashing signal
Open gate, e-stop loop open
48
or failure in feedback circuit or
failure on simulation button
58
Press acknowledge button.
33
Type of button
Feedback circuit for
contacts
external contactors
2 NO contacts
no
2 NO contacts
no
2 NO contacts
no
2 NO contacts
no
2 C/O contacts
no
2 C/O contacts
no
2 NO contacts
yes
2 NO contacts
yes
2 NO contacts
yes
2 C/O contacts
yes
Pair of buttons with
Feedback circuit for
external contactors
Pair 1, button S1,
NO contact
Pair 1, button S1,
common connector
Pair 1, button S1,
common connector
Pair 1, button S1,
contact NF
Pair 1, button S2,
NC contact
Pair 1, button S2,
common connector
Pair 1, button S2,
common connector
Pair 1, button S2,
NO contact
Pair 2, button S1,
NO contact
Pair 2, button S1,
common connector
Pair 2, button S1,
common connector
Pair 2, button S1,
NC contact
Pair 2, button S2,
NC contact
Pair 2, button S2,
Feedback circuit
common connector
Pair 2, button S2,
common connector
Acknowledge button
Pair 2, button S2,
NO contact
Continuous signal
All buttons in initial
position. For a new start
all buttons have to be
activated according to
the starting conditions.
All buttons are
activated,
K1, K2 are energized.
BH 5910 / 200217 / 190A