Safety gates and E-stop (switch 1 in position 4)
With switch 10 the maximum number of gates is selected. Open (unused)
inputs (S_1/S_2 and S_3/S_4) have to be linked with a wire bridge.
K1 and K2 can only be activated, if the e-stop loop is closed and all con-
nected gates have been opened and closed again.
Both gate contacts have to be operated within 3 s. If the time difference is
longer, the gate has to be opened before it can be closed again. When all
gates are closed the unit can also be activated by an external connected
simulation button.
After e-stop or power failure the unit can only be reset by manual start.
If changeover contacts are used on the gate switches the switchover time
has to be less then 50 ms. If it is longer the outputs K1 and K2 are switched
off and the unit gives failure code 7. This failure is stored and can only be
reset by disconnecting the auxiliary supply.
Function diagram
Auxiliary
voltage (A1/A2)
Gate S1 (S11/S12)
Gate S2 (S13/S14)
Gate S3 (S21/S22)
E-stop
Simulation button
(S43/S44)
K1/K2 (13-14,
23-24, 33-34)
48 (gates open
or E-stop)
58 (all gates closed,
e-stop loop closed)
: off
: on
: flashing
Gate monitor and E-stop,
1 gate with 3 NO gate contacts and e-stop loop
All manuals and user guides at all-guides.com
M8442
Settings on switch 10
Number and
No. of
Switch
type of
gates
10
gate switches
0
2
2 NO contacts
1
1
2 C/O contacts
2
1
3 NO contacts
3
2
2 NO contacts
4
1
2 C/O contacts
5
1
3 NO contacts
6-9
position not allowed (failure 5)
NO contacts must be closed when gate is closed, NC contacts must be
open when gate is closed.
Terminal designation
1 gate with
2 gate with
Ter-
3 NO
2 NO
minal
gate contacts
gate contacts
S11
gate 1, S1
gate 1, S1
S12
S14
gate 1, S2
gate 1, S2
S13
S21
gate 1, S3
gate 2, S1
S22
S24
not connected
gate 2, S2
S23
1 E-stop button,
1 Simulation or start button
S31
E-stop, channel 1
S32
S34
E-stop, channel 2
S33
S41
S42
S44
Simulation or start button
S43
Semiconductor outputs
Output
Flashing signal
Open gate, e-stop loop open
48
or failure in feedback circuit or
failure on simulation button
Gates are closed but starting
conditions not fulfilled or E-stop
loop has been opened and closed
58
again.
K1, K2 can be activated with the
simulation button
31
Feedback circuit
Simulation
for external con-
button
tactors
yes
no
yes
no
yes
no
yes
yes
yes
yes
yes
yes
1 gate with
Feedback cir-
2 C/O
cuit for external
gate contacts
contactors
gate 1, S1
NO contact
gate 1, S1
common
connector
gate 1, S1
common
connector
gate 1, S1
NC contact
gate 1, S2
NC contact
gate 1, S2
common
connector
gate 1, S2
common
connector
gate 1, S2
NO contact
Feedback
circuit
Continuous signal
Gates are closed and
contacts K1, K2 are
active
BH 5910 / 200217 / 190A