• The power supply must use the rated voltage according to the machine and a separate
circuit for the air conditioner. The section of the power line must comply with national
requirements.
• When the maximum current of the air conditioner ≥16A, they must use the magnetotherm
or a differential switch with overcurrent protection.
• Normal operating range is 90% ~ 110% of local rated voltage.
• The minimum distance between the air conditioner and fuel elements is 1.5 m.
• The interconnection cord connects the indoor and outdoor units. You must first choose the
right cable size before preparing it for connection.
• The supply cord of appliances for outdoor use shall be between 1,5 and 3m long and
shall be either an extra hard usage or a hard usage cord. (Only for the AC with UL or ETL-
MARKING, UL60335-2-40)
Cable types: Outdoor power cable: H07RN-F or H05RN-F
Interconnection cord: H07RN-F or H05RN-F
(For the AC with CE-MARKING & CB-MARKING, IEC 60335-2-40+A1:2016)
• Minimum Cross-sectional Area of Power cable and interconnection cord.
North America
Appliance Amps (A)
10
13
18
25
30
40
• The size of the interconnection cord, power cable, fuse, and switch needed is determined
by the maximum current of the unit. The maximum current is indicated on the nameplate
located on the side panel of the unit. Refer to this nameplate to choose the right cable, fuse,
or switch.
• Note: The core number of the cable refers to the detailed wiring diagram adhered on the unit
which you purchased.
• Means for disconnection must be incorporated in the fixed wiring in accordance with the
wiring rules.
• In the connection systems of the air conditioning, the electrical line and the interconnection
systems of each individual element, the connection diagrams of the units will prevail.
• The fuse type and standard value prevail over the print mark on the respective controllers
and fuse holders.
Packing list of the indoor unit
Indoor unit
1 set
Remote controller
1 PC
Batteries (#7)
2 PC
Instructions
1 set
Drain pipee
1 PC
*In all accessories, the material objects of the actual packaging prevail, since these may differ depending
on the chosen model.
Notices for installation
Electrical safety requirements
AWG
Rated Current of Appliance (A)
18
>3 and ≤6
16
>6 and ≤10
14
>10 and ≤16
12
>16 and ≤25
10
>25 and ≤32
8
>32 and ≤40
Others
Packing list
18
Other regions
Nominal Cross-Sectional Area
Packing list of the outdoor unit
Outdoor unit
1 set
Plastic strap
1 roll
Pipe protection ring
1 PC
(mm2)
0,75
1
1,5
2,5
4
6