• When mounting the indoor and outdoor units, make sure the power cord is installed at a distance of at least 1 m away from any TV or radio so as
to prevent noise or interference with the images.
• The refrigerant required for the installation is R410A. Make sure the refrigerant is correct before installation. Incorrect refrigerant may cause
the unit to malfunction.
• Do not install the air conditioner in the following places:
1) Where there is oil or gas, such as the kitchen. Otherwise, the plastic parts may age, fall off or water may leak.
2) where there are corrosive gases (such as sulphur dioxide). Corrosion in the copper pipes or welded parts may cause the refrigerant to leak.
3) Where there are machines emitting electromagnetic waves. Electromagnetic waves may interfere with the control system, causing the unit to
malfunction.
4) Where there is a high salt content in the air. When exposed to air with a high salt content, the mechanical parts will experience accelerated
ageing which will severely compromise the service life of the unit.
5) Where there are major voltage fluctuations. Operating the unit using a power supply system that has large voltage fluctuations will reduce the
service life of the electronic components, and cause the unit's controller system to malfunction.
6) Where there is a risk of leakage of flammable gases. Examples are sites that contain carbon fibres or combustible dust in the air, or where there
are volatile combustibles (such as diluent or petrol). The above gases may cause explosion and fire.
7) Do not touch the fins of the heat exchanger as this may lead to injury.
8) Some products use the PP packing belt. Do not pull or tug on the PP packing belt when you transport the product. It will be dangerous if the
packing belt breaks.
9) Note the recycling requirements for nails, wood, carton and other packaging materials. Do not discard these materials directly as these may lead
to bodily harm.
10) Tear up the packaging bag for recycling to prevent children from playing with it, and leading to suffocation.
11)The appliance shall not be installed in the laundry.
• This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.
Accessories
Code
Name of Accessories
Installation manual
1
User manual
2
3
Pipe insulation material
Water outlet joint
4
5
Clasp
Water connecting pipe
6
Adhesive tape for seal
7
Display
8
Weak electric cable group
9
Copper nut
10
Accessories to purchase locally
Code
Name
1
Copper pipe
PVC pipe
2
for water
discharge
Insulation
3
casing for
piping
7.1-28.0kW
7.1-16.0kW
7.1-16.0kW
20.0-28.0kW
40.0-56.0kW
20.0-28.0kW
40.0-56.0kW
7.1-56.0kW
Appearance
Choose and purchase copper pipes that
correspond to the length and size calculated for
the selected model in the installation manual of the
outdoor unit and your actual project requirements.
Refer to specific models.
The inner diameter is based on the diameter of
the copper and PVC pipes. The thickness of the
pipe casing is 10 mm or more. Increase the
thickness of the casing (20 mm or thicker) when
the temperature exceeds 30°C or the humidity
exceeds RH80%.
Q'ty
Outline
(This manual)
1
1
2
1
1
2
1
2
1
1
1
1
Dimensions
2
Usage
Heat insulation
For drainage
Check the joint that connects the drain
hose and the outlet of indoor unit
To connect drain pipe
To connect drain pipe
Use for connecting pipes
Qty
Note
To purchase
Use to connect
based on actual
indoor refrigerant
project
piping.
requirements.
To purchase based
Use to discharge
on actual project
condensed water
requirements.
from the indoor unit.
To purchase
based on actual
Protect piping from
project
condensation.
requirements.