Schedule
Re-tighten power terminal connections to specified torque
2 weeks after installation
Re-tighten power terminal connections to specified torque
3 months after installation
Monthly or After Each
Equalization
For wet cell (flooded type) batteries, make sure the water level
is correct. Wet cell water levels should be checked monthly or
Re-tighten all wiring terminal connections to specified torque
Annually
Inspect the system earth grounding for all components. Verify all
grounding conductors are appropriately secured to earth ground.
Table 4-3. Maintenance Schedule
50
Maintenance Items
values.
values.
Inspect the battery bank. Look for cracked or
bulging cases, and corroded terminals.
according to the manufacturer's
recommendations.
Clean the heatsink fins with a clean, dry rag.
Inspect all wiring for damage or fraying.
Inspect for nesting insects.
values.
Operation
5.0 Networking and Communication
5.1 Introduction
The TriStar MPPT 150V provides several communication options. The TriStar MPPT 150V uses a
proprietary protocol for the MeterBus
network and the non-proprietary open standard MODBUS
TM
and MODBUS TCP/IP
protocols for RS-232, EIA-485, and ethernet networks. Additionally, HTTP,
TM
SMTP, and SNMP are supported for web page, email, and network message support.
Morningstar's MSView
PC software provides system monitoring and logging capabilities via RS-
TM
232, EIA-485, and Ethernet. MSView
PC software is available for free on our website at:
TM
http://www.morningstarcorp.com
Further, hardware and third party software that supports the MODBUS
communicate with a TriStar MPPT 150V.
Multiple communication ports can be used simultaneously. For example, a TriStar MPPT 150V may
be connected to a MeterBus
network for on-site system metering, connected to the internet for
TM
remote monitoring, and connected to an EIA-485 network to bridge data from other controllers in the
system to an internet connection. Note that the RS-232 and EIA-485 connections share hardware and
therefore cannot be used simultaneously.
Table 5-1 below provides a summary of morningstarcorp.com/supported features for each communi-
cation interface.
Display system/network data on a TriStar meter
Connect a TSMPPT to a Relay Driver or other MS Accessory
Connect multiple TSMPPT together in a network
View and log data with MSView
TM
PC Software
View logged data stored in the TriStar MPPT 150V internal memory
Update TriStar MPPT 150V firmware
Program custom settings
View data in a web browser
Email notification
Text Message Alerts
SNMP Alerts
Table 5-1. Communication summary
TriStar MPPT Operator's Manual
TM
protocol can also be used to
TM
51