TECHNICAL DATA
MODEL
Typ
Thermal power
Fuels
Minimum gas pressure (measured at the test point)
Maximum gas pressure
Electrical supply
Fan - capacitor motor
Pump - capacitor motor
Ignition transformer
Pump
Operation
The burner conforms to IP 40 level of insulation as per EN 60529.
FIRING RATE
6
5
4
3
2
1
200
200.000
Minimum output at 1st stage: 116 kW - 10 kg/h
MINIMUM GAS PRESSURE - 2nd STAGE OUTPUT
Pressure: measured at the test point with combustion chamber at 0 mbar.
10
8
6
200
200.000
250
300
240.000
280.000
natural gas (G 20)
LPG (G 31)
250
300
240.000
280.000
116 / 232 - 465 kW 100.000 / 200.000 - 400.000 kcal/h
Oil, max. viscosity at 20 °C: 6 mm
Natural gas with Pci 8.600 kcal/m
LPG with Pci 22.200 kcal/m
Maximum capacity requires:
- 9 mbar with natural gas;
- 9,5 mbar with LPG.
Combustion chamber at 0 mbar.
35 mbar
single-phase 230 V +/- 10% 50 Hz
2.9 A / 230 V - 12.5 µF
1.4 A / 230 V - 6.3 µF
primary 1.8 A / 230 V - secondary 1x 8 kV 30 mA
Output 55 kg/h at 12 bar - max. pressure 15 bar
Two stages
350
400
320.000
360.000
Gas pressure test point
350
400
320.000
360.000
15
GI / EMME 400
496 T1
2
/s (1,5 °E)
3
3
D1967
450
500
400.000
D1968
450
500
kW
kcal/h
400.000
GB
kW
kcal/h
D1956