PROCOM 2 or CYCLIC 2020 regulation - SEC 7HC air treatment type
8
ALARMS
For PROCOM-2:
The alarm page displays the alarms that are still present on the system.
For CYCLIC 2020:
When the LED on the
key is lit, an alarm has occurred.
fault on concerned compressor, may be in connection with:
constant
flashing
hygrometry fault on concerned line
flashing
upper limit fault on concerned compressor
constant
temperature > 40°C in the room
Flashing slowly
temperature < 5°C in the room
constant
hygrometry fault
flashing slowly
regulation pressure fault
back-up cylinder half empty
flashing rapidly
or cylinders activation
mini network pressure fault
constant
maxi network pressure fault
Acknowledgement: press
and
once read.
519015-15
HOSPITAIR CABIN (MV) – 11 & 15 bar
Disjunction
Drain under the cyclone
Version
11 bar
15 bar
(parameter 4) 7.5 bar
8.5 bar
(parameter 5)
100 bar
100 bar
(parameter 9)
7 bar
7.5 bar
(parameter 6)
4.5 bar
6.3 bar
(parameter 7)
10 bar
12.5 bar
simultaneously to acknowledge the alarm
9
MAINTENANCE AND SERVICING
IMPORTANT:
For this operation, use all necessary protective measures (gloves, mask,
overalls etc.) then destroy contamined consumables (antibacterial
cartridges, condensates etc.) in according with that country's applicable
laws (regulation incinerator).
Maintenance is to be entrusted to trained and approved personnel by the
exploiting, with all necessary knowledge and acquainted with best practice.
Not to carry out maintenance operations when the device is in use.
If the spare parts used during maintenance operations are not
corresponding to the manufacturers' requirements, the manufacturer
declines all responsibility in the event of an incident.
The modification of the compressed air plant is forbidden.
Modification of the compressed air plant is forbidden without the approval
of the manufacturer.
If the compressed air plant is modified following manufacturer agreement,
a control and a suitable test must be realized to make sure that the
compressed air plant is always safe to use.
To avoid risk of damage or prevent equipment become dangerous is essential use the
compatible components provide by the manufacturer.