en
0 ... 10 V signal
•
Electric strength 30 V DC/24 V AC
•
Input resistance of the voltage input > 10 kΩ
7.2.4 SSM signal properties
An integrated collective fault signal is applied as a potential-free normally closed contact.
Contact load:
•
Permitted minimum: 12 V AC/DC, 10 mA
•
Permitted maximum: 250 V AC, 1 A, (AC1 power factor > 0.95). 30 V DC, 1 A
DANGER
Risk of fatal electrical shock!
Improper connection of the collective fault signal (SSM) contact poses a risk of fatal injury
due to electric shock!
7.2.5 Signal cable
•
The bare cable end is to be inserted in the system's switchbox. Observe cable assignment!
•
Ensure that the connecting cable does not contact either the pipes or the pump.
Cable assignment
2-wire cable
4-wire cable
The design of the control cable should contain the features of the following table:
Feature
Length for the 0 ... 10 V signal
Length for the PWM signal cable
8
Commissioning
•
Electrical work: Electrical work must be performed by a qualified electrician.
•
Installation/dismantling work: The installation/dismantling must be carried out by a qualified technician
who is trained in the use of the necessary tools and fixation materials.
•
The product must be operated by persons who are instructed on how the complete system functions.
•
Prior to commissioning the pump, check that it has been installed and connected correctly.
•
Ensure that the system is filled with a permissible fluid.
56
Pin
Cable colour
1
brown
2
white or blue
Pin
Cable colour
1
brown
2
white (grey)
3
blue
4
black
Installation and operating instructions • Wilo-Stratos PARA-C/-CZ • Ed.01/2023-04
0 ... 10 V signal
ground (GND)
0 ... 10 V signal
0 ... 10 V signal
ground (GND)
0 ... 10 V signal
SSM
SSM
PWM
ground (GND)
PWM input
PWM
ground (GND)
PWM input
SSM
SSM
Recommended value
max. 15 m
max. 3 m