End; Factory Settings Of The Control Electronics - Burkert Typ 8605 Manuel D'utilisation

Régulateur électronique numérique pour vannes proportionnelles
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Type 8605
Configuration
dnld (download)
When download is selected the parameters stored in the operating unit are transferred to the basic device.
This is only possible, if the version of the data is the same as in the basic device (e. g. data transfer between a
200 - 1000 mA version and a 500 - 2000 mA version is not possible).
After that the operating unit displays "rdY". If the data transfer failed "Err" is displayed.
9.3.11.

end

To quit the respective menu level, select the menu item END with the arrow keys.
The settings made are saved on leaving the configuration menu.
Figure 27:
End
9.4.
factory settings of the control electronics
Menu item
InP
Out / VALV
Out / VAdJ
Out / AdJ
deLY
Cut
PArA
Addr
SPOS
s
Hz
%
SP
HI
PV
V
mA
LO
,
factory setting
0 ...10 V
- - - -
OFF
LO: 2 mA
HI: 200 mA
LO: 0.0 s
HI: 0.0 s
LO: 2.0 %
SEt2
0
0.0 %
comment
Input signal 0 ...10 V selected
No valve selected
Manual fine tuning of the valve fre-
quency inactive
These values are changed by a
valve selection
Ramp function inactive
Zero point cut-off active at 2 %
Controller parameter set 2 selected
Address 0 for the serial communi-
cation selected
Safety setting 0 % at an input
signal below 4 mA (with selection
of the 4 ... 20 mA input signal)
selected
english
33