9.3.9.
spOs (safe position) - setting of the safety position
Input of the safety position (0.0 to 100.0 %) that is controlled with a selected standard signal input of 4 to 20 mA
and a drop below the 4 mA input signal.
Figure 25:
SPOS (Safe position) - Setting of the safety position
The standard signal 4 to 20 mA is the only one that permits a fault to be detected when the input value
drops below 4 mA. In this case it is possible to define which current value is to be controlled (e. g. 50 %)
9.3.10.
data (data) - upload and download
between the operating unit and the basic device
This function is used for data transfer from one operating unit to several basic devices. After connecting the operating
unit, the stored parameters can be transmitted to the basic device.
This function is only available for the cable plug version.
Figure 26:
dAtA (Data)
upld (upload)
When upload is selected the parameters of the basic device are transferred to the operating unit. That means, that
first the memory of the operating unit is cleared and then filled with all relevant data of the basic device. After that
the operating unit displays „rdY" (ready). If the data transfer failed „Err" (error) is displayed.
32
english
Type 8605
Configuration
of parameters